ELE07-01098
| Conference | 4/3/2007 | 4/3/2007 | 4/3/2007 4:17:25 PM | P | DONE |
|
|
CONFERENCE FOR GENERATOR PLEASE CONTACT RON THANK YOU Phone #: ###-#### talked about early morning meeting to discuss load-bank install in available space
|
ELE07-00979
| Final | 4/2/2007 | 4/3/2007 | 4/3/2007 3:37:17 PM | P | PASS |
|
|
bryan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, ok to final
|
ELE07-01101
| Electrical Rough-In | 4/3/2007 | 4/3/2007 | 4/3/2007 3:08:44 PM | P | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall callede contr, left corr notice, nec 300.5 minimum burial depth shall be 18" for non-metallic raceways, 680.10 no u/g wiring shall be within 5' of pool edge, 352.26 there shall not be more than 360 degrees bend in rnc betwee pull points
|
ELE07-01095
| Rough-In Permanent Service | 4/3/2007 | 4/3/2007 | 4/3/2007 2:22:54 PM | P | PASS |
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric ok, p/s u/g n ok
|
ELE07-00815
| Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 1:30:27 PM | P | PASS |
|
|
jim - pls call 30 min prior to inspect; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ric basement only ok
|
ELE07-00889
| Electrical Rough-In | 4/3/2007 | 4/3/2007 | 4/3/2007 12:43:16 PM | P | NR |
|
|
jim Note: underground ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no conduit in place yet, called, elect said forgot to postpone
|
ELE06-04004
| Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 10:33:17 AM | A | CANC |
|
|
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, told owner permit cancelled, he was not happy, said would do as he pleased, and hung up
|
ELE06-03238
| Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 10:30:56 AM | A | NR |
|
|
david ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told owner to finish stapling and need all makeup done
|
ELE07-00459
| Final | 4/3/2007 | 4/3/2007 | 4/3/2007 9:55:38 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/3/2007 at 7:03:02 AM. Contact: ###-####. ok to final, signed occ card
|
ELE07-01088
| Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 9:29:23 AM | A | PASS |
|
|
Contact is Perry. This is for an upgraded UFER ground for the existing service. Phone #: ###-#### ok to cover gec
|
ELE07-00965
| Final | 4/3/2007 | 4/3/2007 | 4/3/2007 9:12:28 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/3/2007 at 5:22:30 AM. Contact: ###-####. ok to final
|
ELE06-04309
| Final | 4/2/2007 | 4/3/2007 | 4/3/2007 8:03:13 AM | P | CANC |
|
|
Contact: Eric Cobiskey Phone #: ###-#### Inspection cancelled from web by: Shelli Daylong
|
ELE07-01003
| Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 8:01:07 AM | A | PART |
|
|
mitch; Phone #: ###-#### Internet Inspection Request from: Victoria Beall walls only ok to cover
|