BLD06-02714
| FIRE-Final Inspection | 4/2/2007 | 4/3/2007 | 4/3/2007 4:45:42 PM | A | PASS |
|
|
c/n items finished, fire life safety finaled.
|
FIR06-01001
| INSP-Final Inspection | 4/2/2007 | 4/3/2007 | 4/3/2007 4:40:39 PM | A | PASS |
|
|
Fire alarm permit work passed field inspection.
|
FIR06-00948
| INSP-Supply line flush | 4/3/2007 | 4/3/2007 | 4/3/2007 4:39:04 PM | P | PART |
|
|
Fire supply line flush completed.
|
FIR06-00523
| INSP-Alarm Testing | 4/3/2007 | 4/3/2007 | 4/3/2007 4:37:56 PM | P | PART |
|
|
See comments per field inspection completed by M. Timmerman.
|
FIR06-00986
| INSP-Sprinkler Rough-in/Hydro | 3/30/2007 | 4/3/2007 | 4/3/2007 4:36:22 PM | A | PART |
|
|
OH rough-in inspection completed for building one, noted some areas in need of correction prior to approval for cover including two heads too close to adjacent walls, heads at two locations that exceed min. spacing requirements, tenting at one head 2nd floor mech. closet is inadequate, need to provide proper coverage at the garage soffits above the water heaters.
|
BLD07-00002
| FIRE-Final Inspection | 4/2/2007 | 4/3/2007 | 4/3/2007 4:26:29 PM | A | PASS |
|
|
Life safety inspection passed.
|