BLD07-02347
| FIRE-Final Inspection | 4/2/2008 | 4/3/2008 | 4/3/2008 4:11:50 PM | A | FAIL |
|
|
During life safety inspection notice new card access was being installed. Contractor will get with fire alarm company so the connection can be tested to the fire alarm and life safety can be finaled.KR
|
BLD08-00427
| FIRE-Final Inspection | 4/2/2008 | 4/3/2008 | 4/3/2008 4:02:01 PM | A | FAIL |
|
|
Crash bar at front door needs to be repaired or replaced. New fire alarm panel installed without a permit being pulled.The original panel was an EST1 the new panel is an EST fire shield, the batterys in The panel are also the wrong size. Door will not close correctly. installing contractor was State fire sales and service of UTAH. This permit will not be finaled until a fire alarm permit has been issued and finaled and crash bar at front door has been corrected. The Owner has been notified of these issues.KR
|
BLD08-00577
| FIRE-Final Inspection | 4/3/2008 | 4/3/2008 | 4/3/2008 2:35:58 PM | P | FAIL |
|
|
Need to install sign over east door: door to remain unlocked while occupied and one fire extinguisher in basement. KR
|
FIR08-00230
| INSP-Final Inspection | 4/2/2008 | 4/3/2008 | 4/3/2008 11:08:47 AM | A | PASS |
|
|
Inspection complete.KR
|
BLD07-01714
| FIRE-Final Inspection | 4/2/2008 | 4/3/2008 | 4/3/2008 11:07:57 AM | A | FAIL |
|
|
Could not complete inspection due to emergency lighting not workig and fire alarm not finaled.KR
|
FIR07-01053
| INSP-Final Inspection | 4/3/2008 | 4/3/2008 | 4/3/2008 11:06:10 AM | P | FAIL |
|
|
All duct detector wiring were open air splices with wire nuts and not installed in back boxes. No other testing performed.KR
|