Inspections for the day of: Tuesday, April 3, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00524 INSP-Sprinkler Rough-in4/2/20124/3/20124/4/2012 2:17:22 PMPPART
Previous C/N items verified for completion. Finished walkthrough for coverage adjustments at the overhead AMH tracks and cubbies. Noted missing coverage at the SW corner of the north half photo bay. Plan modifications pending.
FIR11-00365 INSP-Sprinkler Rough-in4/2/20124/3/20124/4/2012 2:10:45 PMPPART
Plan modification pending.
FIR11-00301 INSP-Sprinkler Rough-in4/2/20124/3/20124/4/2012 2:09:44 PMPPART
Vestibules 000B and 002B are incomplete. Plan modifications pending.
FIR11-00431 INSP-Sprinkler Rough-in4/2/20124/3/20124/4/2012 2:03:20 PMPPART
Inspection items listed 3/30 remain unchanged with the exception of one retainer at the dock and field ceiling tile in place where grid is complete at the non-clean link. Ceilings and sprinkler protection are still lacking at vestibule 100P, closet @ RR 100F, room 100J, column line K, link intersection, and GR100H.
FIR11-00651 INSP-Sprinkler Rough-in/Hydro4/3/20124/3/20124/4/2012 1:27:38 PMPPART
BLD11-00123 FIRE-Final Inspection4/2/20124/3/20124/3/2012 3:39:16 PMPPASS
Previous correction items verified for completion. Life safety inspection passed.
BLD11-00289 FIRE-Final Inspection4/2/20124/3/20124/3/2012 3:37:44 PMPPASS
Racking permit finaled.
BLD12-00635 FIRE-Final Inspection4/2/20124/3/20124/3/2012 3:36:42 PMAFAIL
The type one cooking hood suppression system needs to meet monitoring requirements per IFC 2009 904.3.5.
BLD12-00197 FIRE-Final Inspection4/2/20124/3/20124/3/2012 1:11:40 PMAPART
Temporary occupancy for a period of 30 days approved per R. Gervais. Items for permit final include building service heat at the lower level and a plan modification for the fire alarm system. Location of the remote annunciator was determined acceptable by the Boise Fire Dept.
FIR09-00080 INSP-Final Inspection4/2/20124/3/20124/3/2012 12:46:55 PMAFAIL
Netcon 6 rating at the time of inspection. Noted tamper switch has been repaired and re-tested okay.
FIR12-00155 INSP-Final Inspection4/3/20124/3/20124/3/2012 12:43:29 PMAPART
Final pending reliable building heat source to maintain min. temperature at the lower level per NFPA 13.
FIR12-00142 INSP-Final Inspection4/2/20124/3/20124/3/2012 12:25:06 PMAPASS
Scope of fire alarm work passed inspection. Permit finaled.
FIR09-00080 INSP-Sprinkler Rough-in/Hydro4/2/20124/3/20124/2/2012 4:16:05 PMACANC
Phone #: ###-#### >> Inspection requested via web by Mark Scharfen Inspection cancelled from web by: Mark Scharfen