FIR11-00524
| INSP-Sprinkler Rough-in | 4/2/2012 | 4/3/2012 | 4/4/2012 2:17:22 PM | P | PART |
|
|
Previous C/N items verified for completion. Finished walkthrough for coverage adjustments at the overhead AMH tracks and cubbies. Noted missing coverage at the SW corner of the north half photo bay. Plan modifications pending.
|
FIR11-00365
| INSP-Sprinkler Rough-in | 4/2/2012 | 4/3/2012 | 4/4/2012 2:10:45 PM | P | PART |
|
|
Plan modification pending.
|
FIR11-00301
| INSP-Sprinkler Rough-in | 4/2/2012 | 4/3/2012 | 4/4/2012 2:09:44 PM | P | PART |
|
|
Vestibules 000B and 002B are incomplete. Plan modifications pending.
|
FIR11-00431
| INSP-Sprinkler Rough-in | 4/2/2012 | 4/3/2012 | 4/4/2012 2:03:20 PM | P | PART |
|
|
Inspection items listed 3/30 remain unchanged with the exception of one retainer at the dock and field ceiling tile in place where grid is complete at the non-clean link. Ceilings and sprinkler protection are still lacking at vestibule 100P, closet @ RR 100F, room 100J, column line K, link intersection, and GR100H.
|
FIR11-00651
| INSP-Sprinkler Rough-in/Hydro | 4/3/2012 | 4/3/2012 | 4/4/2012 1:27:38 PM | P | PART |
|
|
|
BLD11-00123
| FIRE-Final Inspection | 4/2/2012 | 4/3/2012 | 4/3/2012 3:39:16 PM | P | PASS |
|
|
Previous correction items verified for completion. Life safety inspection passed.
|
BLD11-00289
| FIRE-Final Inspection | 4/2/2012 | 4/3/2012 | 4/3/2012 3:37:44 PM | P | PASS |
|
|
Racking permit finaled.
|
BLD12-00635
| FIRE-Final Inspection | 4/2/2012 | 4/3/2012 | 4/3/2012 3:36:42 PM | A | FAIL |
|
|
The type one cooking hood suppression system needs to meet monitoring requirements per IFC 2009 904.3.5.
|
BLD12-00197
| FIRE-Final Inspection | 4/2/2012 | 4/3/2012 | 4/3/2012 1:11:40 PM | A | PART |
|
|
Temporary occupancy for a period of 30 days approved per R. Gervais. Items for permit final include building service heat at the lower level and a plan modification for the fire alarm system. Location of the remote annunciator was determined acceptable by the Boise Fire Dept.
|
FIR09-00080
| INSP-Final Inspection | 4/2/2012 | 4/3/2012 | 4/3/2012 12:46:55 PM | A | FAIL |
|
|
Netcon 6 rating at the time of inspection. Noted tamper switch has been repaired and re-tested okay.
|
FIR12-00155
| INSP-Final Inspection | 4/3/2012 | 4/3/2012 | 4/3/2012 12:43:29 PM | A | PART |
|
|
Final pending reliable building heat source to maintain min. temperature at the lower level per NFPA 13.
|
FIR12-00142
| INSP-Final Inspection | 4/2/2012 | 4/3/2012 | 4/3/2012 12:25:06 PM | A | PASS |
|
|
Scope of fire alarm work passed inspection. Permit finaled.
|
FIR09-00080
| INSP-Sprinkler Rough-in/Hydro | 4/2/2012 | 4/3/2012 | 4/2/2012 4:16:05 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Mark Scharfen Inspection cancelled from web by: Mark Scharfen
|