Inspections for the day of: Tuesday, April 3, 2012.
Number of inspections: 7
Percentage of inspections complete: 86 %
Percentage of inspections not complete: 14 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00870 FIRE-Conference3/14/20123/28/2012 A 
Please check on this and let Barb @ permit desk know status-want to try to close out permit-Thanks
BLD12-00459 FIRE-Final Inspection4/3/20124/3/20124/3/2012 3:24:18 PMPPASS
life safety passed
FIR11-00543 INSP-Sprinkler Rough-in4/2/20124/3/20124/3/2012 2:00:17 PMAPART
Some piping can be covered. See the latest copy of the approved plans. But the plans do not reflect the actual piping/head arrangement. This is especially important in the hydraulic remote area #4. Additional elbows have been installed in the sprinkler drops that are not shown on the plans. Per plan review there is hardly any safety factor left over so additional fittings will adversely effect the operation of the sprinklers. Plans need to be resubmitted again showing the correct piping layout prior to a cover inspection being given. The remote area #4 is not the only area where piping does not match. One room has additional pendants and uprights where other rooms have pendants and uprights deleted.
FIR12-00118 INSP-Final Inspection4/2/20124/3/20124/3/2012 1:55:12 PMAFAIL
Provide the Inteli-tap as per plans or resubmit plans deleting it, Provide as-built plans showing the remote annunciator on the oneline as per redline comment, Provide correct remote annunciator, Resubmit plans showing/addressing the manual pull stations/horn/remote annunciator that are located in the west end of the building. The inspection needs to be redone due to no signals being sent. Per the monitoring station the AES panel sent a RAM corrupt/programming required message.
BLD11-00812 FIRE-Final Inspection4/2/20124/3/20124/3/2012 10:51:37 AMAPASS
life safety passed
FIR12-00144 INSP-Final Inspection4/2/20124/3/20124/3/2012 10:51:02 AMAPASS
Permit finaled. The netcon was a 5
FIR12-00144 INSP-Sprinkler Rough-in/Hydro4/2/20124/3/20124/2/2012 4:18:13 PMACANC
Phone #: ###-#### >> Inspection requested via web by Mark Scharfen Inspection cancelled from web by: Mark Scharfen