MIS13-00072
| FIR-Conference | 3/27/2013 | 3/27/2013 | | P | |
|
|
waiting on Stephanie to check documents
|
BLD13-00137
| FIRE-Final Inspection | 4/3/2013 | 4/3/2013 | 4/3/2013 3:47:09 PM | P | PASS |
|
|
Life safety passed. Smoke alarms functioned and the fire extinguishers were ok.
|
FIR13-00109
| INSP-Final Inspection | 4/3/2013 | 4/3/2013 | 4/3/2013 3:24:20 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00108
| INSP-Final Inspection | 4/3/2013 | 4/3/2013 | 4/3/2013 3:22:01 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00107
| INSP-Final Inspection | 4/3/2013 | 4/3/2013 | 4/3/2013 3:21:11 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00574
| INSP-Sprinkler Rough-in | 4/2/2013 | 4/3/2013 | 4/3/2013 3:20:15 PM | A | PASS |
|
|
The 24hr air test on the dry system passed.
|
FIR12-00433
| INSP-Final Inspection | 4/2/2013 | 4/3/2013 | 4/3/2013 3:17:15 PM | A | FAIL |
|
|
The first hvac unit tested did not shutdown upon activation of the duct smoke detector so no others were tested. The DSC communicator installed is not the model number in the submittal package and will need to be submitted for approval. As-builts and map do not match the actual installation with additional devices shown that have not been installed and addressing changes. The sprinkler systems devices did test ok and the correct signals were received at central station.
|