ELE15-00485
| Final | 4/2/2015 | 4/3/2015 | 4/3/2015 3:56:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brad Baker Final ok
|
GCE14-00167
| GCE-Final | 4/3/2015 | 4/3/2015 | 4/3/2015 3:35:26 PM | P | NR |
|
|
Steve ###-#### Contractor to install AC unit and light fixtures at man doors. Owner asked me not to do inspection due to incomplete.
|
ELE15-00844
| Final | 4/2/2015 | 4/3/2015 | 4/3/2015 2:53:07 PM | P | PASS |
|
|
Please call homeowner, Ralph Dean at ###-#### when they are on their way. Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
|
ELE15-00893
| Electrical Rough-In | 4/3/2015 | 4/3/2015 | 4/3/2015 2:30:13 PM | P | PASS |
|
|
Call 1/2 Prior to inspection for Access. thanks mike Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Sunroom on back of house rough in ok cover
|
ELE15-00897
| Electrical Rough-In | 4/3/2015 | 4/3/2015 | 4/3/2015 2:06:57 PM | P | PASS |
|
|
FLOOR RI Phone #: ###-#### Inspection requested via web by JENNY EMEL Under floor all cleaned up, whips removed and blanks installed on complete conduit system under floor. Rough in ok cover
|
ELE14-02952
| Final | 4/2/2015 | 4/3/2015 | 4/3/2015 1:29:47 PM | P | PASS |
|
|
Sorry I wasn''t sure permit number to submit for a final Phone #: ###-#### Inspection requested via web by Brad Baker Shell final ok
|
ELE15-00854
| Final | 4/2/2015 | 4/3/2015 | 4/3/2015 12:30:26 PM | A | PASS |
|
|
HOMEOWNER WILL BE HOME AND AVAILABLE IN THE MORNING AFTER 8:00 AM PLEASE CONTACT HER FOR ANY QUESTIONS @ ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON Final ok
|
ELE15-00528
| Final | 4/1/2015 | 4/3/2015 | 4/3/2015 12:15:44 PM | A | FAIL |
|
|
Greg Milburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 2 receptacle outlets located in shop area still require GFCI protection as per 210.8
|
ELE15-00394
| Final | 4/3/2015 | 4/3/2015 | 4/3/2015 11:49:27 AM | A | PASS |
|
|
Dan Lowry is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
|
ELE15-00374
| Electrical Rough-In | 4/2/2015 | 4/3/2015 | 4/3/2015 11:11:07 AM | A | FAIL |
|
|
Mark Phone #: ###-#### turned into conference. Shall provide adequate box fill, shall maintain 12-2 MN cable on 20 amp circuit, shall change breaker feeding bathroom receptacles to 20 amp, shall secure NM cables with in 12" of boxes, shall install AFCI protection for bedroom receptacles added, shall install tamper resistant receptacles.
|
ELE15-00873
| Conference | 4/2/2015 | 4/3/2015 | 4/3/2015 10:23:55 AM | A | DONE |
|
|
Larry Phone #: ###-####// please call 30 min before Discussed service change on building in back of property off alley way. Shall relocated to provide work space, shall penetrate roof to clear alley with overhead conductors, roof on shop steeper than 4/12 pitch, will be about 24 inches above roof conductor to be more than the 3' above roof required by code immediately.
|
ELE15-00714
| Electrical Rough-In | 4/2/2015 | 4/3/2015 | 4/3/2015 10:03:52 AM | A | PASS |
|
|
Kevin Phone #: ###-#### Underground for service and perimeter bond a single #8 rough in ok cover
|
ELE15-00358
| Final | 4/2/2015 | 4/3/2015 | 4/3/2015 9:46:55 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE15-00867
| Rough-In Permanent Service | 4/2/2015 | 4/3/2015 | 4/3/2015 8:59:22 AM | A | PASS |
|
|
Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
|
ELE15-00408
| Electrical Rough-In | 4/2/2015 | 4/3/2015 | 4/3/2015 8:32:13 AM | A | PASS |
|
|
Wall rough in inspection - Wall in front of Floral area Please call Kyle for any questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott Floral to right of south entrance 1/2 wall rough in ok cover
|