Inspections for the day of: Friday, April 3, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00485 Final4/2/20154/3/20154/3/2015 3:56:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Baker Final ok
GCE14-00167 GCE-Final4/3/20154/3/20154/3/2015 3:35:26 PMPNR
Steve ###-#### Contractor to install AC unit and light fixtures at man doors. Owner asked me not to do inspection due to incomplete.
ELE15-00844 Final4/2/20154/3/20154/3/2015 2:53:07 PMPPASS
Please call homeowner, Ralph Dean at ###-#### when they are on their way. Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
ELE15-00893 Electrical Rough-In4/3/20154/3/20154/3/2015 2:30:13 PMPPASS
Call 1/2 Prior to inspection for Access.
thanks mike Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Sunroom on back of house rough in ok cover
ELE15-00897 Electrical Rough-In4/3/20154/3/20154/3/2015 2:06:57 PMPPASS
FLOOR RI Phone #: ###-#### Inspection requested via web by JENNY EMEL Under floor all cleaned up, whips removed and blanks installed on complete conduit system under floor. Rough in ok cover
ELE14-02952 Final4/2/20154/3/20154/3/2015 1:29:47 PMPPASS
Sorry I wasn''t sure permit number to submit for a final Phone #: ###-#### Inspection requested via web by Brad Baker Shell final ok
ELE15-00854 Final4/2/20154/3/20154/3/2015 12:30:26 PMAPASS
HOMEOWNER WILL BE HOME AND AVAILABLE IN THE MORNING AFTER 8:00 AM PLEASE CONTACT HER FOR ANY QUESTIONS @ ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON Final ok
ELE15-00528 Final4/1/20154/3/20154/3/2015 12:15:44 PMAFAIL
Greg Milburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
2 receptacle outlets located in shop area still require GFCI protection as per 210.8
ELE15-00394 Final4/3/20154/3/20154/3/2015 11:49:27 AMAPASS
Dan Lowry is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
ELE15-00374 Electrical Rough-In4/2/20154/3/20154/3/2015 11:11:07 AMAFAIL
Mark Phone #: ###-#### turned into conference. Shall provide adequate box fill, shall maintain 12-2 MN cable on 20 amp circuit, shall change breaker feeding bathroom receptacles to 20 amp, shall secure NM cables with in 12" of boxes, shall install AFCI protection for bedroom receptacles added, shall install tamper resistant receptacles.
ELE15-00873 Conference4/2/20154/3/20154/3/2015 10:23:55 AMADONE
Larry Phone #: ###-####// please call 30 min before Discussed service change on building in back of property off alley way. Shall relocated to provide work space, shall penetrate roof to clear alley with overhead conductors, roof on shop steeper than 4/12 pitch, will be about 24 inches above roof conductor to be more than the 3' above roof required by code immediately.
ELE15-00714 Electrical Rough-In4/2/20154/3/20154/3/2015 10:03:52 AMAPASS
Kevin Phone #: ###-#### Underground for service and perimeter bond a single #8 rough in ok cover
ELE15-00358 Final4/2/20154/3/20154/3/2015 9:46:55 AMAPASS
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE15-00867 Rough-In Permanent Service4/2/20154/3/20154/3/2015 8:59:22 AMAPASS
Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
ELE15-00408 Electrical Rough-In4/2/20154/3/20154/3/2015 8:32:13 AMAPASS
Wall rough in inspection - Wall in front of Floral area
Please call Kyle for any questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott Floral to right of south entrance 1/2 wall rough in ok cover