Inspections for the day of: Friday, April 3, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00920 INSP-Final Inspection4/1/20154/3/20154/3/2015 4:27:24 PMPDEFR
Overbooked - need advance notice to confirm time and staffing available to complete inspection as requested.
FIR14-00531 INSP-Sprinkler Rough-in4/2/20154/3/20154/3/2015 4:13:14 PMAPART
4th and 5th floor tower 2 sprinkler coverage at soffits units only okayed- need to provide missing fire stop at some locations. Field modifications at the first floor lobby to be reflected on plan mod.
FIR14-00620 INSP-Sprinkler Rough-in4/3/20154/3/20154/3/2015 3:44:40 PMPPART
Brandon Phone #: ###-####
BLD14-03604 FIRE-Final Inspection4/1/20154/3/20154/3/2015 3:29:57 PMPPASS
Life safety inspection passed. Fire extinguisher at the second floor to be posted as discussed. Note- no signature card available on site.
BLD14-03629 FIRE-Final Inspection4/2/20154/3/20154/3/2015 3:06:06 PMANR
Project related fire alarm and sprinkler permit work must be finaled prior to life safety approvals.
FIR15-00138 INSP-Final Inspection4/2/20154/3/20154/3/2015 3:04:18 PMAPEND
Missing project related fire sprinkler permit inspection request and schedule.
FIR15-00180 INSP-Sprinkler Rough-in/Hydro4/2/20154/3/20154/3/2015 3:01:32 PMAPASS
Standpipe hydrostatic test completed satisfactory.
BLD15-00120 FIRE-Final Inspection4/2/20154/3/20154/3/2015 12:18:14 PMAFAIL
Items noted include; repair three exit signs, missing fire extinguisher per plan, door at the common hall is not reflected on approved drawings, project related fire sprinkler work needs finaled, breakroom fire extingusiher is overdue annual certification.
BLD14-03515 FIRE-Final Inspection4/2/20154/3/20154/3/2015 11:16:07 AMAPASS
Fire life safety inspection passed.
FIR15-00133 INSP-Final Inspection4/2/20154/3/20154/3/2015 11:12:18 AMAPASS
Fire sprinkler permit work passed final walkthrough.
BLD15-00876 FIRE-Conference4/2/20154/3/20154/3/2015 9:57:58 AMADONE
On site conference with tenant regarding conditions necessary for an occupancy approval. Noted items include; need to verify fire alarm panel is monitored and trouble condition is cleared, post missing fire extinguishers throughout and at each level as discussed, missing knox box, building address numbers are not satisfactory, repair non-functional door leaf at the main entry/exit.
BLD15-00724 FIRE-Final Inspection4/2/20154/3/20154/3/2015 9:14:32 AMAPASS
Previously noted correction items verified for completion. Life safety passed.