Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00299 INSP-Sprinkler Rough-in/Hydro3/30/20174/3/20174/3/2017 3:02:39 PMPPART
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 7 complete, hotel resident rooms on level 7 approved for cover. Hydrostatic test complete for supply from pump room to floor control valves complete as well as overhead fire sprinkler piping on levels 3, 5, 6 and 7.
FIR17-00155 INSP-Sprinkler Rough-in/Hydro4/3/20174/3/20174/3/2017 2:58:24 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete for area of work, approved for cover.
FIR16-00664 INSP-Final Inspection4/3/20174/3/20174/3/2017 2:29:24 PMPFAIL
Decorative ceiling beams have been installed in west side of kitchen/dining area and master bedroom, deflector position is to close to beams as specified in Table 8.2.5.4.2 of NFPA13D, corrections for mentioned area's will need to be made to pass final inspection. Smoke detector in south east bedroom is to close to sprinkler head, correction will need to be made to pass final inspection. Fire sprinkler head in hallway is painted as well as east sprinkler head in south east bedroom, mentioned heads will need to be replaced for final inspection. Fire bell is not installed on exterior of house. Escutcheons need to be installed for final inspection.
NAF17-00022 INSP-Supply line flush4/3/20174/3/20174/3/2017 1:55:44 PMPPASS
Rough to cover complete for underground, approved for cover, main line flush complete, underground hydrostatic test complete.
FIR16-00557 INSP-Sprinkler Rough-in/Hydro3/31/20174/3/20174/3/2017 11:11:45 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover. Hydrostatic test for overhead fire sprinkler piping/FDC complete.
BLD17-00115 FIRE-Final Inspection3/31/20174/3/20174/3/2017 10:24:22 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection passed/complete.
FIR17-00102 INSP-Sprinkler Rough-in/Hydro3/31/20174/3/20174/3/2017 9:48:48 AMAPART
Partial rough to cover for underground supply stub-in complete (Riser section of underground and piping penetrating the footing) Area inspected approved for cover.
FIR16-00753 INSP-Final Inspection4/3/20174/3/20174/3/2017 9:18:40 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00510 INSP-Final Inspection3/31/20174/3/20174/3/2017 9:18:13 AMAPASS
Final fire sprinkler inspection passed/complete
FIR16-00753 INSP-Alarm Testing3/31/20174/3/20174/3/2017 9:17:45 AMADONE
Alarm testing complete
FIR16-00556 INSP-Sprinkler Rough-in3/31/20174/3/20174/3/2017 8:11:59 AMAPART
Rough to cover inspection for overhead fire sprinkler pipe tenting partially complete, approved for cover except the south east apartment unit of pod 2, level 3, no insualtion installed
FIR17-00154 INSP-Final Inspection3/31/20174/3/20174/3/2017 7:18:07 AMAPASS
Final fire alarm inspection passed/complete