FIR16-00299
| INSP-Sprinkler Rough-in/Hydro | 3/30/2017 | 4/3/2017 | 4/3/2017 3:02:39 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 7 complete, hotel resident rooms on level 7 approved for cover. Hydrostatic test complete for supply from pump room to floor control valves complete as well as overhead fire sprinkler piping on levels 3, 5, 6 and 7.
|
FIR17-00155
| INSP-Sprinkler Rough-in/Hydro | 4/3/2017 | 4/3/2017 | 4/3/2017 2:58:24 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete for area of work, approved for cover.
|
FIR16-00664
| INSP-Final Inspection | 4/3/2017 | 4/3/2017 | 4/3/2017 2:29:24 PM | P | FAIL |
|
|
Decorative ceiling beams have been installed in west side of kitchen/dining area and master bedroom, deflector position is to close to beams as specified in Table 8.2.5.4.2 of NFPA13D, corrections for mentioned area's will need to be made to pass final inspection. Smoke detector in south east bedroom is to close to sprinkler head, correction will need to be made to pass final inspection. Fire sprinkler head in hallway is painted as well as east sprinkler head in south east bedroom, mentioned heads will need to be replaced for final inspection. Fire bell is not installed on exterior of house. Escutcheons need to be installed for final inspection.
|
NAF17-00022
| INSP-Supply line flush | 4/3/2017 | 4/3/2017 | 4/3/2017 1:55:44 PM | P | PASS |
|
|
Rough to cover complete for underground, approved for cover, main line flush complete, underground hydrostatic test complete.
|
FIR16-00557
| INSP-Sprinkler Rough-in/Hydro | 3/31/2017 | 4/3/2017 | 4/3/2017 11:11:45 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover. Hydrostatic test for overhead fire sprinkler piping/FDC complete.
|
BLD17-00115
| FIRE-Final Inspection | 3/31/2017 | 4/3/2017 | 4/3/2017 10:24:22 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection passed/complete.
|
FIR17-00102
| INSP-Sprinkler Rough-in/Hydro | 3/31/2017 | 4/3/2017 | 4/3/2017 9:48:48 AM | A | PART |
|
|
Partial rough to cover for underground supply stub-in complete (Riser section of underground and piping penetrating the footing) Area inspected approved for cover.
|
FIR16-00753
| INSP-Final Inspection | 4/3/2017 | 4/3/2017 | 4/3/2017 9:18:40 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00510
| INSP-Final Inspection | 3/31/2017 | 4/3/2017 | 4/3/2017 9:18:13 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR16-00753
| INSP-Alarm Testing | 3/31/2017 | 4/3/2017 | 4/3/2017 9:17:45 AM | A | DONE |
|
|
Alarm testing complete
|
FIR16-00556
| INSP-Sprinkler Rough-in | 3/31/2017 | 4/3/2017 | 4/3/2017 8:11:59 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler pipe tenting partially complete, approved for cover except the south east apartment unit of pod 2, level 3, no insualtion installed
|
FIR17-00154
| INSP-Final Inspection | 3/31/2017 | 4/3/2017 | 4/3/2017 7:18:07 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|