ELE18-00569
| Electrical Rough-In | 4/2/2018 | 4/3/2018 | 4/3/2018 2:55:58 PM | P | PASS |
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Corrections complete Thank you.
|
ELE18-00569
| Final | 4/3/2018 | 4/3/2018 | 4/3/2018 2:55:43 PM | P | PASS |
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
ELE17-02775
| Electrical Rough-In | 4/3/2018 | 4/3/2018 | 4/3/2018 2:28:57 PM | P | CANC |
|
|
Requesting rough-in inspection for the basement area "worm room". Site contact is Luke Hardy. Phone #: ###-#### Inspection requested via web by Clint Tate Wrong permit requested, needed 222 N 8th str. ELE17-03734
|
ELE17-03734
| Electrical Rough-In | 4/3/2018 | 4/3/2018 | 4/3/2018 2:28:27 PM | P | PASS |
|
|
Discussed show window receptacle requirements. Windows above garage style doors used as windows shall be concidered windows that could be used to advertise and shall have minimum required receptacles installed. NEC definitions. Show Window. Any window, including windows above doors, used or designed to be used for the display of goods or advertising material, whether it is fully or partly enclosed or entirely open at the rear and whether or not it has a platform raised higher than the street floor level. (CMP-2) Warm and dry storage rooms only walls and hardlids rough in ok cover.
|
ELE18-01274
| Electrical Rough-In | 4/3/2018 | 4/3/2018 | 4/3/2018 1:21:34 PM | P | PART |
|
|
Ceiling inspection before ceiling tiles are installed. Phone #: ###-#### Inspection requested via web by Steve Craig 2nd permit exists for this space. Back slanted grid ceiling only rough in ok cover
|
ELE17-04346
| Final | 4/2/2018 | 4/3/2018 | 4/3/2018 11:15:01 AM | A | FAIL |
|
|
Front door may be locked. Please call 30 minutes prior to arrange access Phone #: ###-#### Inspection requested via web by Steve Craig 314.25- Each box shall hae a cover. 2 gang top of stair and exit main level bottom of stair. 408.7- Unused openings shall be closed using an approved method. Breaker blanks in electrical closet left panel.
|
ELE18-01228
| Rough-In Permanent Service | 3/30/2018 | 4/3/2018 | 4/3/2018 10:29:46 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE18-00025
| Final | 4/2/2018 | 4/3/2018 | 4/3/2018 10:05:53 AM | A | FAIL |
|
|
Garage code 8724 Should be 87/1 Park Place Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Smoke detectors shall be wired as per instructions. No power to smokes. 210.52- Walls 24" or wider shall have a receptacle outlet installed. 30" wall in down bed shall be receptacle outlet installed. 314.16- Boxes shall be of an approved size for free conductor space. Box at end of peninsula 8 cu. in. with 11.25 cu. in. installed. 422.30- A means shall be provided to disconnect appliances from power. Hood and microwave. Lockout acceptable.
|
ELE17-04280
| Final | 4/2/2018 | 4/3/2018 | 4/3/2018 10:00:18 AM | A | FAIL |
|
|
Garage Code 8624 Phone #: ###-#### Inspection requested via web by Darryn Coburn 314.16- Boxes shall be of an approved size for free conductor space. Box and end of peninsula 8 cu. in. with 11.25 cu in. installed. 422.30- A means shall be provided to disconnect appliances from power. Hood, microwave. Lockout acceptable.
|