Inspections for the day of: Tuesday, April 3, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00569 Electrical Rough-In4/2/20184/3/20184/3/2018 2:55:58 PMPPASS
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Corrections complete Thank you.
ELE18-00569 Final4/3/20184/3/20184/3/2018 2:55:43 PMPPASS
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
ELE17-02775 Electrical Rough-In4/3/20184/3/20184/3/2018 2:28:57 PMPCANC
Requesting rough-in inspection for the basement area "worm room". Site contact is Luke Hardy. Phone #: ###-#### Inspection requested via web by Clint Tate
Wrong permit requested, needed 222 N 8th str. ELE17-03734
ELE17-03734 Electrical Rough-In4/3/20184/3/20184/3/2018 2:28:27 PMPPASS
Discussed show window receptacle requirements. Windows above garage style doors used as windows shall be concidered windows that could be used to advertise and shall have minimum required receptacles installed.
NEC definitions. Show Window. Any window, including windows above doors, used or designed to be used for the display of goods or advertising material, whether it is fully or partly enclosed or entirely open at the rear and whether or not it has a platform raised higher than the street floor level. (CMP-2)
Warm and dry storage rooms only
walls and hardlids rough in ok cover.
ELE18-01274 Electrical Rough-In4/3/20184/3/20184/3/2018 1:21:34 PMPPART
Ceiling inspection before ceiling tiles are installed. Phone #: ###-#### Inspection requested via web by Steve Craig
2nd permit exists for this space.
Back slanted grid ceiling only rough in ok cover
ELE17-04346 Final4/2/20184/3/20184/3/2018 11:15:01 AMAFAIL
Front door may be locked. Please call 30 minutes prior to arrange access Phone #: ###-#### Inspection requested via web by Steve Craig
314.25- Each box shall hae a cover. 2 gang top of stair and exit main level bottom of stair.
408.7- Unused openings shall be closed using an approved method. Breaker blanks in electrical closet left panel.
ELE18-01228 Rough-In Permanent Service3/30/20184/3/20184/3/2018 10:29:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE18-00025 Final4/2/20184/3/20184/3/2018 10:05:53 AMAFAIL
Garage code 8724
Should be 87/1 Park Place Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Smoke detectors shall be wired as per instructions. No power to smokes.
210.52- Walls 24" or wider shall have a receptacle outlet installed. 30" wall in down bed shall be receptacle outlet installed.
314.16- Boxes shall be of an approved size for free conductor space. Box at end of peninsula 8 cu. in. with 11.25 cu. in. installed.
422.30- A means shall be provided to disconnect appliances from power. Hood and microwave. Lockout acceptable.
ELE17-04280 Final4/2/20184/3/20184/3/2018 10:00:18 AMAFAIL
Garage Code 8624 Phone #: ###-#### Inspection requested via web by Darryn Coburn
314.16- Boxes shall be of an approved size for free conductor space. Box and end of peninsula 8 cu. in. with 11.25 cu in. installed.
422.30- A means shall be provided to disconnect appliances from power. Hood, microwave. Lockout acceptable.