ELE17-03442
| Electrical Rough-In | 4/2/2018 | 4/3/2018 | 4/3/2018 2:20:02 PM | P | PASS |
|
|
Mark Phone #: ###-#### Walls on 1st floor and 2nd floor parapet receptacles ok to cover
|
ELE18-01104
| Electrical Rough-In | 4/2/2018 | 4/3/2018 | 4/3/2018 2:19:03 PM | P | FAIL |
|
|
Please call my husband Brett Rankin to meet you at the home, he has done all the work. Thank you, Bethahy Phone #: ###-#### Inspection requested via web by Bethany Rankin 210.11 Receptacles in bathroom shall be 20 amp rated
|
ELE17-04259
| Final | 4/2/2018 | 4/3/2018 | 4/3/2018 11:43:18 AM | A | PASS |
|
|
P;I new 100 amp panel for existing space access after 9:30 contact Darren 208.807.5122 Phone #: ###-#### Inspection requested via web by David Feller Up residential unit final only ok
|
ELE17-04257
| Final | 4/2/2018 | 4/3/2018 | 4/3/2018 11:42:44 AM | A | FAIL |
|
|
First Floor Apartment and Building Service for Fault Current labeling access after 9:30 am contact Darren 208.807.5122 for walk thru Phone #: ###-#### Inspection requested via web by David Feller 1) Tamper resistant receptacles 2) Light fixtures over shelfing shall be removed 3) Lockable disc for water heater Need seperate ELE for unit in floral shop and will transfer rough-in inspection
|
ELE18-01259
| Rough-In Permanent Service | 4/2/2018 | 4/3/2018 | 4/3/2018 11:37:59 AM | A | PASS |
|
|
Please call Jose Guerrero with coordinating access to home. Phone #: ###-#### Inspection requested via web by Jose Guerrero p/s o/h rec ok
|
ELE18-01266
| Temporary Service | 4/2/2018 | 4/3/2018 | 4/3/2018 9:13:31 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Grounding electrode not driven in the ground all the way, about 5' sticking out
|