Inspections for the day of: Friday, April 3, 2020.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01203 Final4/3/20204/3/20204/3/2020 2:13:05 PMPFAIL
Final inspection for elevator / chair lift electrical only - elevator / chair lift installed by others Bruce is on site - call hi, when you arrive and he will give you instructions on location of chair lift Phone #: ###-#### Inspection requested via web by JENNY EMEL
620.5- Work clearances for lift disconnecting means shall comply with 110.26. Fused disconnect located 6' back inside beautiful metal door and frame work. A rail is located in the middle of disconnecting means.
620.51(C)- Lift disconnecting means shall be located where readily accessible. Around corner towards meter base ok due to very limited space.
ELE19-04799 Electrical Rough-In4/3/20204/3/20204/3/2020 1:28:17 PMPPASS
Elevated concrete deck rough in
4th floor deck over alley area Phone #: ###-#### Inspection requested via web by Jason Parke
Area noted pour rough in ok cover
ELE19-00601 Electrical Rough-In4/3/20204/3/20204/3/2020 12:44:57 PMPCANC
2nd Floor Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Unable to perform inspection due to site is on a suspended job site list received 4-2-2020. General contractor to clear suspension which we will receive a confirmation notice and then have electrical contractor request inspections.
ELE19-01688 Electrical Rough-In4/3/20204/3/20204/3/2020 12:41:42 PMPPASS
Other electrodes such as underground water pipe and building steel will make up a grounding electrode system. Notes due to large amount of debris in area 3/0 bare copper conductor is positioned.
Conrete encased electrode rough in ok cover.
ELE19-01688 Rough-In Permanent Service4/2/20204/3/20204/3/2020 10:03:50 AMACANC
This is actually a Ufer ground inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Called contact and informed this building permit is suspended job site list posted 4-2-2020. Asked to photo installation and recall when ready.
ELE20-00001 Final4/2/20204/3/20204/3/2020 10:00:05 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00002 Final4/2/20204/3/20204/3/2020 9:59:36 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00003 Final4/2/20204/3/20204/3/2020 9:59:08 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00004 Final4/2/20204/3/20204/3/2020 9:58:43 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00005 Final4/2/20204/3/20204/3/2020 9:58:17 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00006 Final4/2/20204/3/20204/3/2020 9:57:47 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00007 Final4/2/20204/3/20204/3/2020 9:57:21 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00008 Final4/2/20204/3/20204/3/2020 9:56:51 AMAPASS
cleared // Steve Phone #: ###-####
As per 345 permit ok to final as payment is made in a large lump sum which takes time to post. Final ok
ELE20-00956 Rough-In Permanent Service4/2/20204/3/20204/3/2020 9:54:29 AMAPASS
Contact is Derek Ball Phone #: ###-#### Inspection requested via web by Scott Campbell Pedistal to East of Loess Pl. p/s u/g n ok
ELE19-01688 Electrical Rough-In4/2/20204/3/20204/3/2020 9:53:01 AMACANC
Rough-In Walls for G level Phone #: ###-#### Inspection requested via web by Scott Campbell Called contact and informed this building permit is on the suspended job lite list posted
4-2-2020. Asked them to take several photos and recall for Monday when the normal inspector is scheduled to be back at work.
ELE20-01145 Conference4/2/20204/3/20204/3/2020 9:06:16 AMPCANC
NEED CONSULTATION PLEASE. House had a fire. Need consultation to get it up to code. Thank you, Have a bless weekend, Phone #: ###-#### >> Inspection requested via web by Kyle Lott Inspection cancelled from web by: Kyle Lott