Inspections for the day of: Monday, April 30, 2001.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-01173 Final4/27/20014/30/20014/30/2001 12:00:00 AMAFAIL
fn insp-- ron ###-####-- call 1st before insp needs switch phase and neutral wires, and remove cabinets from above panel 4/30/2001 9:49:13 AM
ELE01-01138 Final4/27/20014/30/20014/30/2001 12:00:00 AMANR
fn --greg-- ###-#### --call1 1st before insp contractor said he needs P M inspection in stead of A M inspection 4/30/2001 12:35:14 PM
ELE01-00268 Final4/27/20014/30/20014/30/2001 12:00:00 AMAFAIL
greg ###-#### fn - conference only ok 4/30/2001 11:05:06 AM
ELE01-01382 Temporary Service4/30/20014/30/20014/30/2001 12:00:00 AMPPASS
t/s o/h new ok 4/30/2001 1:01:59 PM
ELE01-00423 Rough-In Permanent Service4/30/20014/30/20014/30/2001 12:00:00 AMPFAIL
ALLEN ###-#### cor. posted called 300-4 for high and low voltage cables 210-52(a) kitchen
wall space under window area, 250-24 terminate GEC at neutral bus, 250-66 size bond to water system with proper size conductor 4/30/2001 3:24:12 PM
ELE01-00422 Rough-In Permanent Service4/30/20014/30/20014/30/2001 12:00:00 AMPFAIL
ALLEN###-#### see PM# ele01-00423 for details 4/30/2001 3:34:11 PM
ELE01-01220 Final4/30/20014/30/20014/30/2001 12:00:00 AMPFAIL
###-#### still needs to remove a/c lines from below p/s bond hot a7cold with #4 seal ko s guy mast so it opposes the strain of service drop 4/30/2001 2:11:53 PM
ELE01-01138 Electrical Rough-In4/30/20014/30/20014/30/2001 12:00:00 AMPNR
Scheduled by Inspector: 315 On 4/30/2001 12:33:24 PM contractor called , not ready 4/30/2001 4:35:05 PM