Inspections for the day of: Tuesday, April 30, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00510 INSP-Final Inspection4/29/20024/30/20024/30/2002 12:00:00 AMACANC
Bruce called and said that the fire alarm was not ready 4/30/2002 2:21:17 PM
BLD02-00124 FIRE-Final Inspection4/29/20024/30/20024/30/2002 12:00:00 AMAPASS
fire life/safety OK 4/30/2002 9:24:28 AM
BLD01-02240 FIRE-Hydro test above ground4/29/20024/30/20024/30/2002 12:00:00 AMPPART
Hydro test not done. I did a rough-in inspection on the 1 hour photo, pharmacy and the drive thru canopy. Sprinkler contractor to add one hanger in canopy and change out one pendant in 1 hour photo and pharmacy to ECOH type 4/30/2002 11:33:15 AM
BLD02-00060 FIRE-Final Inspection4/30/20024/30/20024/30/2002 12:00:00 AMPPASS
fire life/safety and fire sprinklers for the vanilla finish OK 4/30/2002 12:08:59 PM
BLD02-00296 FIRE-Final Inspection4/30/20024/30/20024/30/2002 12:00:00 AMPFAIL
verify that the key box on the south exterior wall is the approved fire dept box. If not provide a "Knox Box" per the review comments, mount fire extinguisher at 48" AFF, exterior door in library needs approved hardware, provide fire alarm plans 4/30/2002 2:18:53 PM
BLD00-01151 FIRE-Final Inspection4/30/20024/30/20024/30/2002 12:00:00 AMPPASS
fire life/safety finaled 4/30/2002 10:31:28 AM
FIR01-00562 INSP-Sprinkler Rough-in/Hydro4/30/20024/30/20024/30/2002 12:00:00 AMPPASS
zone 12 and 13 underground flush and hydro test OK (6" and 12") 5/1/2002 12:41:10 PM
FIR01-00354 INSP-Final Inspection4/30/20024/30/20024/30/2002 12:00:00 AMPFAIL
relocate two smoke deectors in classrooms, add smoke detector in electrical room change programing for hvac shutdown upon any smoke detector activation 4/30/2002 4:55:14 PM
FIR02-00050 INSP-Final Inspection4/30/20024/30/20024/30/2002 12:00:00 AMPPASS
Fire sprinklers finaled
FIR02-00115 INSP-Final Inspection4/30/20024/30/20024/30/2002 12:00:00 AMPPASS
Fire sprinkler system finaled