FIR03-00086
| INSP-Final Inspection | 4/28/2003 | 4/30/2003 | 4/30/2003 12:00:00 AM | A | FAIL |
|
|
Provide map, signals that arrive at the monitoring company do not match the signals sent. All zones existing and new need verified to match. The supposed duct detector zone came in as a refrigerent trouble 4/30/2003 4:05:29 PM
|
FIR02-00476
| INSP-Conference | 4/29/2003 | 4/30/2003 | 4/30/2003 12:00:00 AM | A | DONE |
|
|
todd; Phone #: ###-#### Contractor says it will be difficult to mount the manual pull station within 5' of the door as per code. I told him he will need fire dept permission to put it elsewhere. Also one induct detector will be deleted 4/30/2003 10:36:08 AM
|
BLD02-02200
| FIRE-Final Inspection | 4/30/2003 | 4/30/2003 | 4/30/2003 12:00:00 AM | A | PASS |
|
|
Fire alarm system finaled. OK for perm occupancy
|
FIR03-00120
| INSP-Final Inspection | 4/30/2003 | 4/30/2003 | 4/30/2003 12:00:00 AM | P | PASS |
|
|
JOHN; Phone #: ###-#### Fire sprinkler system finaled 4/30/2003 2:19:57 PM
|
BLD03-00161
| FIRE-Final Inspection | 4/29/2003 | 4/30/2003 | 4/30/2003 12:00:00 AM | P | FAIL |
|
|
Items on the previous correction notice have not been corrected 4/30/2003 3:22:37 PM
|