FIR04-00033
| FIR-Aging Inspection | 4/30/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | | PASS |
|
|
fire alarm finaled 4/30/2004 3:13:02 PM
|
FIR04-00089
| INSP-Alarm Testing | 4/29/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | A | FAIL |
|
|
Remove all existing fire alarm equipment. Smoke detectors are overspaced in accounting (devices 23 & 24) and corridor (device 5). A/V overspaced in corridor by west stairs in basement. Install pull station (device 2) in conference center. 4/30/2004 9:09:43 AM
|
FIR04-00165
| INSP-Final Inspection | 4/29/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers finaled 4/30/2004 10:11:56 AM
|
BLD03-02393
| FIRE-Final Inspection | 4/29/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | A | FAIL |
|
|
provide review notes for plan review. Provide sticker at the main entrance/exit. provide door hardware. Provide building address. test duct smoke detectors. Provide ada hardware on the pocket doors 4/30/2004 10:06:18 AM
|
FIR04-00170
| INSP-Final Inspection | 4/29/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | A | PASS |
|
|
fire sprinkler finaled 4/30/2004 9:27:10 AM
|
MIS04-00004
| FIR-Final | 4/29/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | A | FAIL |
|
|
still needs exit sign repaired or removed 4/30/2004 9:26:55 AM
|
FIR03-00525
| INSP-Final Inspection | 4/30/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | P | FAIL |
|
|
The fire sprinkler work performed is ok but the existing fire sprinkler monitoring system does not have a smoke detector over the panel. There is a manual pull near the front of the store as well as two horns near the front. Provide approved drawings showing the addition of the smoke detector 4/30/2004 4:00:45 PM
|
FIR04-00172
| INSP-Alarm Testing | 4/30/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled 4/30/2004 2:48:13 PM
|
MIS04-00004
| FIR-Final | 4/30/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | P | PASS |
|
|
life safety finaled 4/30/2004 1:19:14 PM
|
BLD03-02393
| FIRE-Final Inspection | 4/30/2004 | 4/30/2004 | 4/30/2004 12:00:00 AM | P | PART |
|
|
A temporary occupancy was given with dave millers permission. Items to be completed are: provide remote led's for the duct detectors and retest. provide ada approved door hardware on the pocket doors and provide correct sticker at the main exit 4/30/2004 3:31:16 PM 4/30/2004 3:32:05 PM
|