Inspections for the day of: Friday, April 30, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00033 FIR-Aging Inspection4/30/20044/30/20044/30/2004 12:00:00 AM PASS
fire alarm finaled 4/30/2004 3:13:02 PM
FIR04-00089 INSP-Alarm Testing4/29/20044/30/20044/30/2004 12:00:00 AMAFAIL
Remove all existing fire alarm equipment. Smoke detectors are overspaced in accounting (devices 23 & 24) and corridor (device 5). A/V overspaced in corridor by west stairs in basement. Install pull station (device 2) in conference center. 4/30/2004 9:09:43 AM
FIR04-00165 INSP-Final Inspection4/29/20044/30/20044/30/2004 12:00:00 AMAPASS
fire sprinklers finaled 4/30/2004 10:11:56 AM
BLD03-02393 FIRE-Final Inspection4/29/20044/30/20044/30/2004 12:00:00 AMAFAIL
provide review notes for plan review. Provide sticker at the main entrance/exit. provide door hardware. Provide building address. test duct smoke detectors. Provide ada hardware on the pocket doors 4/30/2004 10:06:18 AM
FIR04-00170 INSP-Final Inspection4/29/20044/30/20044/30/2004 12:00:00 AMAPASS
fire sprinkler finaled 4/30/2004 9:27:10 AM
MIS04-00004 FIR-Final4/29/20044/30/20044/30/2004 12:00:00 AMAFAIL
still needs exit sign repaired or removed 4/30/2004 9:26:55 AM
FIR03-00525 INSP-Final Inspection4/30/20044/30/20044/30/2004 12:00:00 AMPFAIL
The fire sprinkler work performed is ok but the existing fire sprinkler monitoring system does not have a smoke detector over the panel. There is a manual pull near the front of the store as well as two horns near the front. Provide approved drawings showing the addition of the smoke detector 4/30/2004 4:00:45 PM
FIR04-00172 INSP-Alarm Testing4/30/20044/30/20044/30/2004 12:00:00 AMPPASS
Fire alarm finaled 4/30/2004 2:48:13 PM
MIS04-00004 FIR-Final4/30/20044/30/20044/30/2004 12:00:00 AMPPASS
life safety finaled 4/30/2004 1:19:14 PM
BLD03-02393 FIRE-Final Inspection4/30/20044/30/20044/30/2004 12:00:00 AMPPART
A temporary occupancy was given with dave millers permission. Items to be completed are: provide remote led's for the duct detectors and retest. provide ada approved door hardware on the pocket doors and provide correct sticker at the main exit 4/30/2004 3:31:16 PM 4/30/2004 3:32:05 PM