Inspections for the day of: Friday, April 30, 2010.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00444 Final4/29/20104/30/20104/30/2010 3:51:50 PMPPASS
Inspection requested from web by: Stephen Kren Phone #: ###-#### called, ok to final
ELE09-02450 Final4/30/20104/30/20104/30/2010 3:20:53 PMPPASS
ross - please call 1/2 hr prior Phone #: ###-#### ok to final
ELE10-00452 Electrical Rough-In4/29/20104/30/20104/30/2010 3:07:13 PMPPASS
Jacob Phone #: ###-#### corrections made, ric ok
ELE10-00893 Rough-In Permanent Service4/30/20104/30/20104/30/2010 2:19:23 PMPCANC
Inspection requested from web by: Bob Glenn Phone #: ###-#### wrong type request, see ri
ELE10-00893 Electrical Rough-In4/30/20104/30/20104/30/2010 2:05:44 PMPPASS
Inspection requested from web by: Bob Glenn Phone #: ###-#### corrections made, ric ok
ELE10-00825 Final4/30/20104/30/20104/30/2010 1:33:43 PMPPASS
Trent Phone #: ###-#### ok to final, signed occupancy card, no esc
ELE10-00153 Electrical Rough-In4/30/20104/30/20104/30/2010 12:20:08 PMPFAIL
david - basement Phone #: ###-#### met general, needs to finish make-up, move bath receptacle, add receptacle for 12 foot spacing, secure nm cable at light boxes
ELE10-00435 Final4/28/20104/30/20104/30/2010 10:47:24 AMACANC
Final out project.Ken Heller Inspection requested from web by: Ken Heller Phone #: ###-#### called, could not get together, will recall 1st part next week
ELE10-00615 Final4/29/20104/30/20104/30/2010 10:45:33 AMAPASS
Inspection requested from web by: John VanZandt Phone #: ###-#### ok to final, no esc
ELE10-00893 Rough-In Permanent Service4/29/20104/30/20104/30/2010 10:23:24 AMACANC
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### see ri and p/s
ELE10-00893 Electrical Rough-In4/30/20104/30/20104/30/2010 10:22:12 AMAFAIL
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 shall protect cables within 6' of attic access, Note: shall make corrections within 5 working days
ELE10-00893 Permanent Service4/30/20104/30/20104/30/2010 9:52:10 AMAPASS
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### p/s u/g n ok
ELE10-00125 Final4/29/20104/30/20104/30/2010 9:47:51 AMAPASS
chris Phone #: ###-#### ok to final, receptacle installed
ELE10-00938 Electrical Rough-In4/29/20104/30/20104/30/2010 9:09:57 AMAPASS
please final this when you are finished.
Thanks, Dan ###-####. Inspection requested from web by: Dan Mitchell Phone #: ###-#### ric ok
ELE10-00938 Final4/30/20104/30/20104/30/2010 9:09:44 AMAPASS
please final this when you are finished.
Thanks, Dan ###-####. Inspection requested from web by: Dan Mitchell Phone #: ###-#### ok to final
ELE10-00873 Electrical Rough-In4/28/20104/30/20104/30/2010 8:35:48 AMAFAIL
mark Phone #: ###-#### 0r ###-#### met owner, told to bond metal deck parts, add circuit schedule, change receptacle to weather resistant type, will recall for final
ELE10-00733 Final4/29/20104/30/20104/30/2010 8:03:03 AMAPASS
Contact Shane Korte before going so he can meet you there please Inspection requested from web by: Deb Gooden Phone #: ###-#### ok to final, no esc