ELE10-00444
| Final | 4/29/2010 | 4/30/2010 | 4/30/2010 3:51:50 PM | P | PASS |
|
|
Inspection requested from web by: Stephen Kren Phone #: ###-#### called, ok to final
|
ELE09-02450
| Final | 4/30/2010 | 4/30/2010 | 4/30/2010 3:20:53 PM | P | PASS |
|
|
ross - please call 1/2 hr prior Phone #: ###-#### ok to final
|
ELE10-00452
| Electrical Rough-In | 4/29/2010 | 4/30/2010 | 4/30/2010 3:07:13 PM | P | PASS |
|
|
Jacob Phone #: ###-#### corrections made, ric ok
|
ELE10-00893
| Rough-In Permanent Service | 4/30/2010 | 4/30/2010 | 4/30/2010 2:19:23 PM | P | CANC |
|
|
Inspection requested from web by: Bob Glenn Phone #: ###-#### wrong type request, see ri
|
ELE10-00893
| Electrical Rough-In | 4/30/2010 | 4/30/2010 | 4/30/2010 2:05:44 PM | P | PASS |
|
|
Inspection requested from web by: Bob Glenn Phone #: ###-#### corrections made, ric ok
|
ELE10-00825
| Final | 4/30/2010 | 4/30/2010 | 4/30/2010 1:33:43 PM | P | PASS |
|
|
Trent Phone #: ###-#### ok to final, signed occupancy card, no esc
|
ELE10-00153
| Electrical Rough-In | 4/30/2010 | 4/30/2010 | 4/30/2010 12:20:08 PM | P | FAIL |
|
|
david - basement Phone #: ###-#### met general, needs to finish make-up, move bath receptacle, add receptacle for 12 foot spacing, secure nm cable at light boxes
|
ELE10-00435
| Final | 4/28/2010 | 4/30/2010 | 4/30/2010 10:47:24 AM | A | CANC |
|
|
Final out project.Ken Heller Inspection requested from web by: Ken Heller Phone #: ###-#### called, could not get together, will recall 1st part next week
|
ELE10-00615
| Final | 4/29/2010 | 4/30/2010 | 4/30/2010 10:45:33 AM | A | PASS |
|
|
Inspection requested from web by: John VanZandt Phone #: ###-#### ok to final, no esc
|
ELE10-00893
| Rough-In Permanent Service | 4/29/2010 | 4/30/2010 | 4/30/2010 10:23:24 AM | A | CANC |
|
|
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### see ri and p/s
|
ELE10-00893
| Electrical Rough-In | 4/30/2010 | 4/30/2010 | 4/30/2010 10:22:12 AM | A | FAIL |
|
|
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 shall protect cables within 6' of attic access, Note: shall make corrections within 5 working days
|
ELE10-00893
| Permanent Service | 4/30/2010 | 4/30/2010 | 4/30/2010 9:52:10 AM | A | PASS |
|
|
THANKS, HAVE A GOOD DAY!! Inspection requested from web by: Bob Glenn Phone #: ###-#### p/s u/g n ok
|
ELE10-00125
| Final | 4/29/2010 | 4/30/2010 | 4/30/2010 9:47:51 AM | A | PASS |
|
|
chris Phone #: ###-#### ok to final, receptacle installed
|
ELE10-00938
| Electrical Rough-In | 4/29/2010 | 4/30/2010 | 4/30/2010 9:09:57 AM | A | PASS |
|
|
please final this when you are finished. Thanks, Dan ###-####. Inspection requested from web by: Dan Mitchell Phone #: ###-#### ric ok
|
ELE10-00938
| Final | 4/30/2010 | 4/30/2010 | 4/30/2010 9:09:44 AM | A | PASS |
|
|
please final this when you are finished. Thanks, Dan ###-####. Inspection requested from web by: Dan Mitchell Phone #: ###-#### ok to final
|
ELE10-00873
| Electrical Rough-In | 4/28/2010 | 4/30/2010 | 4/30/2010 8:35:48 AM | A | FAIL |
|
|
mark Phone #: ###-#### 0r ###-#### met owner, told to bond metal deck parts, add circuit schedule, change receptacle to weather resistant type, will recall for final
|
ELE10-00733
| Final | 4/29/2010 | 4/30/2010 | 4/30/2010 8:03:03 AM | A | PASS |
|
|
Contact Shane Korte before going so he can meet you there please Inspection requested from web by: Deb Gooden Phone #: ###-#### ok to final, no esc
|