BLD13-00997
| FIRE-Final Inspection | 4/30/2013 | 4/30/2013 | 4/30/2013 3:55:53 PM | P | FAIL |
|
|
Provide annual inspection for the fire extinguisher and provide exit sign at the exterior door as per the review comments.
|
BLD13-01008
| FIRE-Final Inspection | 4/30/2013 | 4/30/2013 | 4/30/2013 3:51:42 PM | P | FAIL |
|
|
Provide annual inspection for fire extinguishers, provide racking/high piled storage permit for all racking exceeding 8'-0", provide exit signs at exterior doors as per plans.
|
FIR13-00086
| INSP-Final Inspection | 4/29/2013 | 4/30/2013 | 4/30/2013 3:03:34 PM | P | PART |
|
|
Fire alarm device testing in the LSO area passed inspection.
|
FIR13-00194
| INSP-Final Inspection | 4/30/2013 | 4/30/2013 | 4/30/2013 2:51:41 PM | P | PASS |
|
|
Permit finaled. Hood suppression system functioned correctly
|
FIR13-00181
| INSP-Sprinkler Rough-in | 4/30/2013 | 4/30/2013 | 4/30/2013 2:48:25 PM | P | PASS |
|
|
Rough-in passed. Sprinkler piping is ok to cover. Two pendants. in two locations, are located too close to one another and will need to be relocated. Will be checked at final.
|
BLD13-00861
| FIRE-Final Inspection | 4/29/2013 | 4/30/2013 | 4/30/2013 2:28:12 PM | A | PASS |
|
|
life safety passed
|
FIR12-00685
| INSP-Final Inspection | 4/29/2013 | 4/30/2013 | 4/30/2013 2:16:15 PM | A | PASS |
|
|
Permit finaled. Monitoring was not set up correctly. Fire dept dispatch was not set up, zone descriptions were wrong and the site address was wrong. I waited while things were corrected.
|
BLD12-01698
| FIRE-Final Inspection | 4/26/2013 | 4/30/2013 | 4/30/2013 2:04:17 PM | A | PASS |
|
|
life safety passed
|
FIR13-00030
| INSP-Final Inspection | 4/29/2013 | 4/30/2013 | 4/30/2013 2:00:59 PM | A | PASS |
|
|
permit finaled
|
FIR13-00030
| INSP-Sprinkler Rough-in | 4/29/2013 | 4/30/2013 | 4/30/2013 1:58:20 PM | A | PASS |
|
|
Overhead hydro test and forward flush passed
|
FIR13-00135
| INSP-Sprinkler Rough-in | 4/29/2013 | 4/30/2013 | 4/30/2013 1:55:46 PM | A | PASS |
|
|
Sprinkler piping in the LOC area is ok to cover.
|
BLD12-02551
| FIRE-Final Inspection | 4/29/2013 | 4/30/2013 | 4/30/2013 10:06:27 AM | A | FAIL |
|
|
Provide an exit sign, emergency lighting and exit discharge lighting as per approved plan or discuss with plan review. Remove all thumbturn dead bolts as discussed and per approved plans. Key is allowed at the main exit all other need to be single action.
|
FIR13-00145
| INSP-Sprinkler Rough-in | 4/29/2013 | 4/30/2013 | 4/30/2013 9:57:28 AM | A | PASS |
|
|
Sprinkler piping is ok to cover.
|