Inspections for the day of: Tuesday, April 30, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00997 FIRE-Final Inspection4/30/20134/30/20134/30/2013 3:55:53 PMPFAIL
Provide annual inspection for the fire extinguisher and provide exit sign at the exterior door as per the review comments.
BLD13-01008 FIRE-Final Inspection4/30/20134/30/20134/30/2013 3:51:42 PMPFAIL
Provide annual inspection for fire extinguishers, provide racking/high piled storage permit for all racking exceeding 8'-0", provide exit signs at exterior doors as per plans.
FIR13-00086 INSP-Final Inspection4/29/20134/30/20134/30/2013 3:03:34 PMPPART
Fire alarm device testing in the LSO area passed inspection.
FIR13-00194 INSP-Final Inspection4/30/20134/30/20134/30/2013 2:51:41 PMPPASS
Permit finaled. Hood suppression system functioned correctly
FIR13-00181 INSP-Sprinkler Rough-in4/30/20134/30/20134/30/2013 2:48:25 PMPPASS
Rough-in passed. Sprinkler piping is ok to cover. Two pendants. in two locations, are located too close to one another and will need to be relocated. Will be checked at final.
BLD13-00861 FIRE-Final Inspection4/29/20134/30/20134/30/2013 2:28:12 PMAPASS
life safety passed
FIR12-00685 INSP-Final Inspection4/29/20134/30/20134/30/2013 2:16:15 PMAPASS
Permit finaled. Monitoring was not set up correctly. Fire dept dispatch was not set up, zone descriptions were wrong and the site address was wrong. I waited while things were corrected.
BLD12-01698 FIRE-Final Inspection4/26/20134/30/20134/30/2013 2:04:17 PMAPASS
life safety passed
FIR13-00030 INSP-Final Inspection4/29/20134/30/20134/30/2013 2:00:59 PMAPASS
permit finaled
FIR13-00030 INSP-Sprinkler Rough-in4/29/20134/30/20134/30/2013 1:58:20 PMAPASS
Overhead hydro test and forward flush passed
FIR13-00135 INSP-Sprinkler Rough-in4/29/20134/30/20134/30/2013 1:55:46 PMAPASS
Sprinkler piping in the LOC area is ok to cover.
BLD12-02551 FIRE-Final Inspection4/29/20134/30/20134/30/2013 10:06:27 AMAFAIL
Provide an exit sign, emergency lighting and exit discharge lighting as per approved plan or discuss with plan review. Remove all thumbturn dead bolts as discussed and per approved plans. Key is allowed at the main exit all other need to be single action.
FIR13-00145 INSP-Sprinkler Rough-in4/29/20134/30/20134/30/2013 9:57:28 AMAPASS
Sprinkler piping is ok to cover.