Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00385 Final4/30/20144/30/20145/1/2014 2:52:09 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt
Contractor to add receptical outlet to leftof oven to satify 210.52. rest of house ok. Final ok
ELE12-00651 ELE-Aging Inspection4/30/20144/30/20144/30/2014 4:13:42 PM DONE
Finalled 1-29-14. I will close permit
ELE12-00651 Final4/30/20144/30/20144/30/2014 4:13:32 PMPPASS
Final ok 1-29-14 by Daryl Degrange
ELE12-00777 ELE-Aging Inspection4/30/20144/30/20144/30/2014 4:11:49 PM DONE
Still under construction
MIS14-00064 ELE-Conference4/30/20144/30/20144/30/2014 3:44:54 PMPDONE
no elec permit covered Met with general or acting forman for general, informed me a electrical contractor has been doing work and plans to pull permit for work to be done on service. As of 4-30-14 work has been performed in kitchen area prior to permit being pulled. Switches added and recess lighting added. Double fee accessed.
ELE13-03529 Final4/30/20144/30/20144/30/2014 2:34:45 PMPPASS
Phone #: ###-#### >> Inspection requested via web by ron spen cer Final ok
ELE14-00671 Final4/29/20144/30/20144/30/2014 10:29:10 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Spencer McLean Final ok
ELE14-00859 Final4/29/20144/30/20144/30/2014 10:05:01 AMAPASS
call Art with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Final ok
GCE14-00047 GCE-Final4/29/20144/30/20144/30/2014 9:25:21 AMANR
Aaron ###-#### Kahala Electric Added a bathroom which is at rough in stage
GCE14-00047 GCE-Rough-In4/30/20144/30/20144/30/2014 9:25:13 AMPPASS
Aaron ###-#### Kahala Electric Bathroom rough in ok cover
ELE14-00385 Final4/30/20144/30/20144/30/2014 9:10:01 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by John VanZandt
410.16(A)(1)- Luminaires located in closet shall have a totally enclosed lamps.
410.16(C)(1)- Incandescent luminaire shall clear storage shelf by minimum of 12".
BCC- High efficiency lamps shall be install in at leat 50% of perminantly installed light fixtures.
210.52(C)(1)- Receptical outlets shall be installed so that no point measured along wall line is more than 24" to receptical outlet serving counter top.