ELE12-02747
| ELE-Aging Inspection | 4/30/2015 | 4/30/2015 | 4/30/2015 5:00:16 PM | | DONE |
|
|
too busy
|
ELE12-02755
| ELE-Aging Inspection | 4/30/2015 | 4/30/2015 | 4/30/2015 4:59:48 PM | | DONE |
|
|
too busy
|
ELE07-03492
| ELE-Aging Inspection | 4/30/2015 | 4/30/2015 | 4/30/2015 4:59:21 PM | | DONE |
|
|
too busy
|
ELE15-01209
| Electrical Rough-In | 4/29/2015 | 4/30/2015 | 4/30/2015 4:57:02 PM | P | PASS |
|
|
call dave with questions, this is for the basement rough in walls Phone #: ###-#### Inspection requested via web by Don Lustig r/i bsmt. walls ok
|
ELE15-00554
| Final | 4/30/2015 | 4/30/2015 | 4/30/2015 4:16:35 PM | P | PASS |
|
|
Robert Phone #: ###-#### final ok
|
ELE15-00554
| Electrical Rough-In | 4/30/2015 | 4/30/2015 | 4/30/2015 4:16:08 PM | P | PASS |
|
|
Robert Phone #: ###-#### r/i ok power to new c/u and airhandeler
|
ELE13-03105
| Final | 4/30/2015 | 4/30/2015 | 4/30/2015 3:46:02 PM | P | PASS |
|
|
Final not temp closing out permit pulling new one for the rest of the job Phone #: ###-#### Inspection requested via web by matt miller corrections made final ok
|
GCE15-00061
| GCE-Permanent Service | 4/30/2015 | 4/30/2015 | 4/30/2015 2:57:23 PM | P | PASS |
|
|
Shawn ###-#### p/s o/h n ok
|
GCE14-00189
| GCE-Final | 4/30/2015 | 4/30/2015 | 4/30/2015 2:42:55 PM | P | NH |
|
|
Laura ###-#### no access please leave TENANTS phone # next time or meet us there
|
ELE15-01191
| Electrical Rough-In | 4/28/2015 | 4/30/2015 | 4/30/2015 2:15:15 PM | P | PASS |
|
|
please inspect floor boxes. Phone #: ###-#### Inspection requested via web by ERIC CENTERS underslab raceways and floor boxes r/i ok to cover
|
ELE15-01226
| Final | 4/30/2015 | 4/30/2015 | 4/30/2015 1:59:34 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Daniel Schaffeld needed p/s
|
ELE15-01226
| Permanent Service | 4/30/2015 | 4/30/2015 | 4/30/2015 1:59:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Daniel Schaffeld p/s o/h rec ok
|
ELE14-03246
| Electrical Rough-In | 4/29/2015 | 4/30/2015 | 4/30/2015 1:36:12 PM | P | PASS |
|
|
Dave. Tower #3 Corridor Soffits 3rd ; 4th floors. Phone #: ###-#### Inspection requested via web by Sean DeLacy tower 1 and 2 corridors 100% tower 3 2nd flr corridor r/i ok
|
ELE15-00797
| Temporary Service | 4/27/2015 | 4/30/2015 | 4/30/2015 12:45:45 PM | P | FAIL |
|
|
JR - husband Phone #: ###-#### #4 alum ground wire required with feeders to house. Entrance hub required in top of service panel for riser. Plastic bushings required with #4 conductors or larger. Ground rods need to be minimum of 6 foot apart. Add 2nd ground rod at house. Separate ground wires and nuetral wires at house panel. Call in for perm. service when ready.
|
ELE14-03386
| Final | 4/29/2015 | 4/30/2015 | 4/30/2015 11:04:45 AM | A | PASS |
|
|
Please contact Max Black to gain access @ ###-#### or ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON final ok
|
ELE15-01080
| Rough-In Permanent Service | 4/29/2015 | 4/30/2015 | 4/30/2015 10:14:43 AM | A | PASS |
|
|
Keith Phone #: ###-#### r/i ok bathrm. receptacles and HRun p/s o/h rec ok Look for supplemental ground rod at final insp.
|
GCE15-00069
| GCE-Rough-In Permanent Service | 4/29/2015 | 4/30/2015 | 4/30/2015 9:22:04 AM | A | FAIL |
|
|
Rowdy ###-#### secondary conduit not installed, nailplate needed west bdrm., 210.52(A)(1)- receptacles shall be installed so there is no more than 6foot between them
|
GCE15-00068
| GCE-Permanent Service | 4/29/2015 | 4/30/2015 | 4/30/2015 8:44:34 AM | A | PASS |
|
|
Terry ###-#### p/s u/g n ok
|