MEC15-01831
| Final | 4/30/2015 | 4/30/2015 | 4/30/2015 4:48:42 PM | P | PASS |
|
|
Make last call of the day. James is contact. Thanks! Phone #: ###-#### Inspection requested via web by Brenda St Clair
|
MEC15-01834
| Pressure Test | 4/30/2015 | 4/30/2015 | 4/30/2015 4:23:18 PM | P | PART |
|
|
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello - 20lb gas pass for range only
|
MEC14-03448
| Rough-in | 4/29/2015 | 4/30/2015 | 4/30/2015 3:42:08 PM | P | PART |
|
|
LOBBY COVER Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate duct work, okay to cover shaft at stair tower 1
|
MEC15-01829
| Final | 4/29/2015 | 4/30/2015 | 4/30/2015 3:01:26 PM | P | PASS |
|
|
Jeramy should be ready by 1pm. Thanks! Phone #: ###-#### Inspection requested via web by Brenda St Clair
|
MEC15-01638
| Final | 4/28/2015 | 4/30/2015 | 4/30/2015 2:23:12 PM | P | PASS |
|
|
installer Sam ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich
|
MEC14-03585
| Final | 4/30/2015 | 4/30/2015 | 4/30/2015 1:44:30 PM | P | PASS |
|
|
please call Rader 1 hour ahead of time. ###-#### Phone #: ###-#### Inspection requested via web by Dan Otero
|
MEC15-01470
| Pressure Test | 4/29/2015 | 4/30/2015 | 4/30/2015 1:27:19 PM | P | PASS |
|
|
Please call Daryl w/ any questions. Phone #: ###-#### Inspection requested via web by Diane Day - 20lb gas, 5lb flue pass
|
MEC14-03564
| Final | 4/29/2015 | 4/30/2015 | 4/30/2015 11:42:58 AM | A | PASS |
|
|
Chad this is Aaron could you call me so we can talk about this. Eric said he would tell you just making sure. Phone #: ###-#### Inspection requested via web by john shay - The outdoor kitchen will be finished at a later time under it's own permit.
|
MEC15-01723
| Final | 4/29/2015 | 4/30/2015 | 4/30/2015 10:55:56 AM | A | PASS |
|
|
Please be late morning early afternoon with a call to Tori ###-#### or Tyrel ###-####. Thanks Phone #: ###-#### Inspection requested via web by Allie Courter
|
MEC15-00417
| Final | 4/29/2015 | 4/30/2015 | 4/30/2015 10:26:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero
|
MEC15-00277
| Final | 4/29/2015 | 4/30/2015 | 4/30/2015 9:47:35 AM | A | FAIL |
|
|
final - call Brandon Nitchals for escort Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Need 1" clearance to combustable on B-vent for water heater. B-vent for water heater runs through a return air plenum, need to install a sealed pipe or chase around the b-vent pipe. Need to install p-trap on RTU condensate drain.
|
MEC15-01820
| Rough-in | 4/29/2015 | 4/30/2015 | 4/30/2015 9:22:59 AM | A | PASS |
|
|
Please call Kellie, the homeowner, to give as much notice as possible to gain access. Her number is ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Dan Otero
|
MEC13-04628
| Mec-Aging Inspection | 4/30/2015 | 4/30/2015 | 4/30/2015 8:50:44 AM | | FAIL |
|
|
Expired
|
MEC13-04628
| DOC - Permit Expired | 4/30/2015 | 4/30/2015 | 4/30/2015 8:49:08 AM | A | PASS |
|
|
Expired
|
MEC14-02385
| Rough-in | 4/29/2015 | 4/30/2015 | 4/30/2015 8:47:03 AM | A | PART |
|
|
Grease Duct Inspection - Please call Mike with any further questions 208.412.6629 Phone #: ###-#### Inspection requested via web by Bailey Esposito - 1st layer fire wrap okay on vertical grease duct.
|
MEC15-01820
| Rough-in | 4/29/2015 | 4/30/2015 | 4/29/2015 5:07:43 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Otero Inspection cancelled from web by: Dan Otero
|