FIR15-00262
| INSP-Sprinkler Rough-in | 4/30/2015 | 4/30/2015 | 4/30/2015 3:39:23 PM | P | FAIL |
|
|
Soffit with two new pendants was fully enclosed, and pipe drops was not able to be seen. Contractor to expose pipes and reschedule.
|
FIR14-00281
| INSP-Final Inspection | 4/29/2015 | 4/30/2015 | 4/30/2015 2:56:02 PM | A | PART |
|
|
Functional test of alarm system complete. Verified previous correction notice items completed satisfactory. Final pending initiating device map posted at FACP and dedicated alarm panel circuit breaker locked out.
|
FIR14-00912
| INSP-Sprinkler Rough-in/Hydro | 4/30/2015 | 4/30/2015 | 4/30/2015 2:51:31 PM | P | CANC |
|
|
Cancelled due to inspection load
|
FIR15-00200
| INSP-Final Inspection | 4/29/2015 | 4/30/2015 | 4/30/2015 1:59:55 PM | A | PASS |
|
|
Scope of work complete. Permit Finaled
|
BLD15-00193
| FIRE-Final Inspection | 4/29/2015 | 4/30/2015 | 4/30/2015 10:09:12 AM | A | PASS |
|
|
Fire life safety pass.
|
FIR15-00245
| INSP-Final Inspection | 4/29/2015 | 4/30/2015 | 4/30/2015 10:08:40 AM | A | PASS |
|
|
Scope of work complete. Strobes moved to appropriate height per code and adjusted for adequate coverage. Permit finaled.
|
FIR15-00125
| INSP-Final Inspection | 4/29/2015 | 4/30/2015 | 4/29/2015 3:42:16 PM | A | PASS |
|
|
Inspection completed on 4/29/15. Scope of work complete. Verified all heads are now standard response 200 degree. Permit finaled.
|