Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00529 INSP-Sprinkler Rough-in4/28/20154/30/20154/30/2015 12:00:00 AMPPART
Pump test went ok. However, the pump room is missing emergency lighting, heater all alarm work. The FDC is not installed. The sprinklers for the pump room were not installed. There was a leak in the union to the jockey pump.

The pump was NOT tested for alarm contacts since no alarm work had been permitted.



Jason// pump and air test- NEEDS Specific time- please call ahead Phone #: ###-####

Schedule pump test for 2:00