ELE13-00310
| ELE-Aging Inspection | 4/30/2018 | 4/30/2018 | 5/7/2018 2:11:45 PM | | FAIL |
|
|
No attemp to final No responce to notice
|
ELE17-04308
| Rough-In Permanent Service | 4/27/2018 | 4/30/2018 | 5/1/2018 7:40:12 AM | P | CANC |
|
|
Trent-insp to get service to controll cabanets Phone #: ###-####
|
ELE17-04308
| Electrical Rough-In | 4/30/2018 | 4/30/2018 | 4/30/2018 2:24:40 PM | P | FAIL |
|
|
Trent-insp to get service to controll cabanets Phone #: ###-#### 300.4G Where raceways containing #4 or larger, shall be protected by an identified insulated fitting. (Feeders to MCP)
|
ELE18-00937
| Final | 4/30/2018 | 4/30/2018 | 4/30/2018 2:20:16 PM | P | PASS |
|
|
Ben Phone #: ###-#### Final ok
|
ELE18-00784
| Final | 4/30/2018 | 4/30/2018 | 4/30/2018 1:10:09 PM | P | PASS |
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk corrections made final ok
|
ELE18-01398
| Rough-In Permanent Service | 4/27/2018 | 4/30/2018 | 4/30/2018 12:45:50 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn
|
ELE18-01398
| Electrical Rough-In | 4/30/2018 | 4/30/2018 | 4/30/2018 12:45:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Walls and hard lid through out rough in ok
|
ELE17-00177
| Electrical Rough-In | 4/30/2018 | 4/30/2018 | 4/30/2018 12:15:55 PM | P | PASS |
|
|
Floor heat mst bath insp Phone #: ###-#### Inspection requested via web by John VanZandt master floor heat only ok to cover
|
ELE18-01584
| Final | 4/27/2018 | 4/30/2018 | 4/30/2018 10:23:17 AM | A | PASS |
|
|
It is all outside. If you have any questions please feel free to contact Justin ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Final ok
|
ELE18-01375
| Final | 4/30/2018 | 4/30/2018 | 4/30/2018 10:19:05 AM | P | CANC |
|
|
Please call Todd when you are on your way Phone #: ###-#### >> Inspection requested via web by Kendra Lanham Inspection cancelled from web by: Kendra Lanham
|
ELE18-00608
| Final | 4/27/2018 | 4/30/2018 | 4/30/2018 9:58:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Final ok
|
ELE17-03804
| Electrical Rough-In | 4/27/2018 | 4/30/2018 | 4/30/2018 9:47:14 AM | A | PASS |
|
|
MItch Phone #: ###-#### garage and sunroom ok to cover
|
ELE18-01450
| Rough-In Permanent Service | 4/27/2018 | 4/30/2018 | 4/30/2018 9:31:58 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot 210.11C4 Garage recep circuit shall have no other. (251.120 Equipment grounding Conductor and 250.142 Use of grounded conductor as equipment ground. Sub panel needs equipment ground) 210.52E Each porch, balcony and deck shall have recep( Fornt Porch) Finish securing and stubbing exterior lighting.
|