Inspections for the day of: Tuesday, April 30, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01563 Electrical Rough-In4/29/20194/30/20194/30/2019 2:40:25 PMPPASS
Call ahead and we can have someone there to let you in. Phone #: ###-#### Inspection requested via web by Dylan Pierce
Kitchen and hobby room off garage ok to cover
ELE19-00747 Final4/29/20194/30/20194/30/2019 2:39:43 PMPPART
Final inspection on Units 105, 107, 108 and 109. Nick Prieto is on site for questions and access. Phone #: ###-#### Inspection requested via web by Tod Lane
Units as requested partial final ok
ELE19-01570 Electrical Rough-In4/30/20194/30/20194/30/2019 2:38:36 PMPPASS
Richard Phone #: ###-####
Detached garage only ok to cover
Owner will delete one breaker to go away from 6 throws without having a main breaker
ELE19-01570 Conference4/30/20194/30/20194/30/2019 2:37:36 PMPCANC
Richard Phone #: ###-####
ELE19-01054 Final4/29/20194/30/20194/30/2019 12:59:59 PMPPASS
Phone #: ###-#### Inspection requested via web by Dan Hobdey
Final ok
ELE19-01016 Electrical Rough-In4/29/20194/30/20194/30/2019 10:17:48 AMAPASS
Concrete floor Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Corrections fixed as noted
Concrete floor boxes ad conduit ok to cover
ELE17-01463 Final4/29/20194/30/20194/30/2019 9:19:39 AMAPASS
May not be there but you know where the pole is! Phone #: ###-#### Inspection requested via web by Ivan Nanney
Final ok
ELE17-01467 Final4/26/20194/30/20194/30/2019 9:12:46 AMACANC
Agreed upon time of 9:00 AM Phone #: ###-#### Inspection requested via web by Christophe Keys
Duplicate request
ELE17-01467 Final4/26/20194/30/20194/30/2019 9:12:08 AMAFAIL
Agreed upon time of 9:00 AM Phone #: ###-#### Inspection requested via web by Christophe Keys
210.8 All receptacles serving counter top shall be GFCI protected
406 All recetpacles shall be tamper proof
314 All boxes recessed in tile shall have a listed type box extender
11.25 Lockable disc for hard wired appliances(dishwasher)
Re check all devices for GFCI protection
Receptacle for micro is free floating behind micro