ELE20-01345
| Final | 4/28/2020 | 4/30/2020 | 4/30/2020 2:38:19 PM | P | FAIL |
|
|
Nate Phone #: 208-###-####.... no contractors onsite
Boise City ordinance require a midpoint rough inspection before job complete and final inspection requested building permit needs attached to electrical permit
solar shall be removed to ground to verify material and able to see grounding of grid
|
ELE20-01455
| Conference | 4/27/2020 | 4/30/2020 | 4/30/2020 2:34:01 PM | P | PASS |
|
|
*screened* Extending mast, exterior only. Please call to schedule time, homeowner not working from home - Douglas Phone #: ###-####...
discussed service location to deck and roofing
|
ELE19-04036
| Final | 4/30/2020 | 4/30/2020 | 4/30/2020 12:20:11 PM | P | PASS |
|
|
Install 1 wall sign reading Continuum. Phone #: ###-#### Inspection requested via web by Ken Olsen...complete...ok to final
|
ELE20-01026
| Final | 4/30/2020 | 4/30/2020 | 4/30/2020 12:19:13 PM | P | PASS |
|
|
Run one 120 volt circuit from the breaker panel to the sign location. Phone #: ###-#### Inspection requested via web by Ken Olsen...job complete...inspection done thru emailed pics as business is closed due to COVID19 restrictions..ok to final
|
ELE19-03961
| Rough-In Permanent Service | 4/29/2020 | 4/30/2020 | 4/30/2020 11:57:24 AM | A | PASS |
|
|
service and rough for 1st floor units and shaft liners Phone #: ###-#### Inspection requested via web by Todd Hall... units ok to cover brezeway drops ok p/s u/g new ok...2 meterpac locations..33 meters
|
ELE20-00930
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:11:18 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) wiring neat and workman like manner...110.12 2) NMB wiring...334.30
|
ELE20-00931
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:10:56 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) wiring neat and workman like manner...110.12 2) NMB wiring...334.30
|
ELE20-00932
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:10:34 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) wiring neat and workman like manner...110.12 2) NMB wiring...334.30
|
ELE20-00933
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:09:17 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) wiring neat and workman like manner...110.12 2) NMB wiring 334.30
|
ELE20-00934
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:08:00 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley.. 1) work complete...connectors not tight 2) neat and workman like manner...110.12 3) NMB wiring...334.30
|
ELE20-00935
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:06:17 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) wiring neat and workman like manner...110.12 2) NMB wiring...334.30 3) tear in sheating of NMB cable shall be replaced 4) grounded conductor being used as ungrounded conductor shall be marked
|
ELE20-00936
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 11:03:44 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) grounded conductor shall be marked properly when used as a ungrounded conductor 2) NMB cable shall be ran so there is a 1 1/4' distance away from face of framing...multiple locations 3) NMB cable shall layflat and not stapled on edge...334.30 4) wiring shall be done in a neat and workman like manner...110.12
|
ELE20-00937
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/30/2020 10:59:09 AM | A | FAIL |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley... 1) wire connection shall be complete...junction in attic connector complete...110.12 2) romex shall be supported and securded to code..334.30 3) wiring shall be done in a neat and workmanlike manner...110.12
|
ELE20-01144
| Final | 4/29/2020 | 4/30/2020 | 4/30/2020 8:45:17 AM | A | PASS |
|
|
Final ; final grid inspection access 1027 Phone #: ###-#### Inspection requested via web by David Nelson...ok to final
|
ELE20-01144
| Electrical Rough-In | 4/30/2020 | 4/30/2020 | 4/30/2020 8:45:09 AM | A | PASS |
|
|
Final ; final grid inspection access 1027 Phone #: ###-#### Inspection requested via web by David Nelson...grid ok to cover
|
ELE20-01468
| Temporary Service | 4/30/2020 | 4/30/2020 | 4/30/2020 8:15:27 AM | A | PASS |
|
|
Corrections Have Been Made And It A Good Please Give Me A Call About This Pole Thanks So Much Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett... t/s o/h new ok
|
ELE20-01448
| Final | 4/29/2020 | 4/30/2020 | 4/29/2020 2:52:34 PM | A | PASS |
|
|
Our electrician Aric Barrera sent Tom Saunders some pictures to pass this inspection. Calling it in online so it can be closed. Aric: ###-#### / Office ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks... inspection done thru pics as per COVID19 requirements and occupied house
|
ELE20-00930
| Electrical Rough-In | 4/29/2020 | 4/30/2020 | 4/29/2020 7:52:12 AM | P | CANC |
|
|
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### >> Inspection requested via web by Bryan Lawley Inspection cancelled from web by: Bryan Lawley
|