Inspections for the day of: Thursday, April 30, 2020.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01345 Final4/28/20204/30/20204/30/2020 2:38:19 PMPFAIL
Nate Phone #: 208-###-####....
no contractors onsite

Boise City ordinance require a midpoint rough inspection before job complete and final inspection requested
building permit needs attached to electrical permit

solar shall be removed to ground to verify material and able to see grounding of grid
ELE20-01455 Conference4/27/20204/30/20204/30/2020 2:34:01 PMPPASS
*screened* Extending mast, exterior only. Please call to schedule time, homeowner not working from home - Douglas Phone #: ###-####...

discussed service location to deck and roofing
ELE19-04036 Final4/30/20204/30/20204/30/2020 12:20:11 PMPPASS
Install 1 wall sign reading Continuum. Phone #: ###-#### Inspection requested via web by Ken Olsen...complete...ok to final
ELE20-01026 Final4/30/20204/30/20204/30/2020 12:19:13 PMPPASS
Run one 120 volt circuit from the breaker panel to the sign location. Phone #: ###-#### Inspection requested via web by Ken Olsen...job complete...inspection done thru emailed pics as business is closed due to COVID19 restrictions..ok to final
ELE19-03961 Rough-In Permanent Service4/29/20204/30/20204/30/2020 11:57:24 AMAPASS
service and rough for 1st floor units and shaft liners Phone #: ###-#### Inspection requested via web by Todd Hall...
units ok to cover
brezeway drops ok
p/s u/g new ok...2 meterpac locations..33 meters
ELE20-00930 Electrical Rough-In4/29/20204/30/20204/30/2020 11:11:18 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) wiring neat and workman like manner...110.12
2) NMB wiring...334.30
ELE20-00931 Electrical Rough-In4/29/20204/30/20204/30/2020 11:10:56 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) wiring neat and workman like manner...110.12
2) NMB wiring...334.30
ELE20-00932 Electrical Rough-In4/29/20204/30/20204/30/2020 11:10:34 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) wiring neat and workman like manner...110.12
2) NMB wiring...334.30
ELE20-00933 Electrical Rough-In4/29/20204/30/20204/30/2020 11:09:17 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) wiring neat and workman like manner...110.12
2) NMB wiring 334.30
ELE20-00934 Electrical Rough-In4/29/20204/30/20204/30/2020 11:08:00 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley..
1) work complete...connectors not tight
2) neat and workman like manner...110.12
3) NMB wiring...334.30
ELE20-00935 Electrical Rough-In4/29/20204/30/20204/30/2020 11:06:17 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) wiring neat and workman like manner...110.12
2) NMB wiring...334.30
3) tear in sheating of NMB cable shall be replaced
4) grounded conductor being used as ungrounded conductor shall be marked
ELE20-00936 Electrical Rough-In4/29/20204/30/20204/30/2020 11:03:44 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) grounded conductor shall be marked properly when used as a ungrounded conductor
2) NMB cable shall be ran so there is a 1 1/4' distance away from face of framing...multiple locations
3) NMB cable shall layflat and not stapled on edge...334.30
4) wiring shall be done in a neat and workman like manner...110.12
ELE20-00937 Electrical Rough-In4/29/20204/30/20204/30/2020 10:59:09 AMAFAIL
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### Inspection requested via web by Bryan Lawley...
1) wire connection shall be complete...junction in attic connector complete...110.12
2) romex shall be supported and securded to code..334.30
3) wiring shall be done in a neat and workmanlike manner...110.12
ELE20-01144 Final4/29/20204/30/20204/30/2020 8:45:17 AMAPASS
Final ; final grid inspection
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson...ok to final
ELE20-01144 Electrical Rough-In4/30/20204/30/20204/30/2020 8:45:09 AMAPASS
Final ; final grid inspection
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson...grid ok to cover
ELE20-01468 Temporary Service4/30/20204/30/20204/30/2020 8:15:27 AMAPASS
Corrections Have Been Made And It A Good Please Give Me A Call About This Pole Thanks So Much Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett...
t/s o/h new ok
ELE20-01448 Final4/29/20204/30/20204/29/2020 2:52:34 PMAPASS
Our electrician Aric Barrera sent Tom Saunders some pictures to pass this inspection. Calling it in online so it can be closed. Aric: ###-#### / Office ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks...
inspection done thru pics as per COVID19 requirements and occupied house
ELE20-00930 Electrical Rough-In4/29/20204/30/20204/29/2020 7:52:12 AMPCANC
Solar Pre-Wire for Future Solar System. Call Jed with any questions at 801.875.3714. Separate Building and Electrical Permit will be pulled. Phone #: ###-#### >> Inspection requested via web by Bryan Lawley Inspection cancelled from web by: Bryan Lawley