FIR19-00261
| INSP-Sprinkler Rough-in/Hydro | 4/30/2020 | 4/30/2020 | 4/30/2020 2:59:24 PM | P | DONE |
|
|
Main line flush is complete, plans need to be submitted to reflect the addition of a dedicated fire line, water delivery is no longer a domestic shared system.
under ground flush // Ron Phone #: ###-####
|
FIR19-00743
| INSP-Sprinkler Rough-in | 4/29/2020 | 4/30/2020 | 4/30/2020 12:48:08 PM | A | PART |
|
|
Rough to cover inspection for corridor bwteen gym and main building complete to include office off of same hallway, area inspected approved for cover.
Contact Tanner Loomis ###-#### 30 Min prior to RTC Insp. start please, inspection is for "C" side .
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR20-00047
| INSP-Sprinkler Rough-in/Hydro | 4/29/2020 | 4/30/2020 | 4/30/2020 11:12:18 AM | P | CANC |
|
|
Inspection request cancelled per conversation with point of contact, point of contact noticed overspacing issues with walls that go to the deck causing upright coverage issues, inspection will be rescheduled for a later date.
Richard Clark is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00225
| INSP-Final Inspection | 4/29/2020 | 4/30/2020 | 4/30/2020 9:40:48 AM | A | PASS |
|
|
Inspection completed by emailed photos of the scope of work, based off of photos final inspection for scope of work is complete.
virtual inspection requested // Steve Phone #: ###-####
|
FIR20-00017
| INSP-Conference | 4/29/2020 | 4/30/2020 | 4/30/2020 9:39:42 AM | A | DONE |
|
|
Fire conference is complete, after discussing with Lee the conclusion for the roof hatch pocket area in the basement is not going to require a smoke detector as discussed.
questions for the B26 remodel project Phone #: ###-#### Inspection requested via web by Trevor Reed
|
FIR20-00141
| INSP-Sprinkler Rough-in | 4/29/2020 | 4/30/2020 | 4/29/2020 2:17:18 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work is complete, approved for cover.
Please call Rick with questions.
Phone #: ###-#### Inspection requested via web by Jeff Packham
|