Inspections for the day of: Wednesday, April 4, 2001.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00079 INSP-Sprinkler Rough-in4/3/20014/4/20014/4/2001 12:00:00 AMAPART
Jim Page ###-#### okay o cover main entry and preaction system (computer room) 4/4/2001 10:04:52 AM
FIR00-00670 INSP-Final Inspection4/3/20014/4/20014/4/2001 12:00:00 AMAPASS
###-####
BLD00-01642 FIRE-Final Inspection4/4/20014/4/20014/4/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 4/4/2001 9:05:22 AM
BLD00-03031 FIRE-Final Inspection4/4/20014/4/20014/4/2001 12:00:00 AMPPASS
fire fn john ###-#### extinguisehr to be tagged for structural inspector and door hardware at front door 4/4/2001 4:00:11 PM
BLD00-00498 FIRE-Final Inspection4/4/20014/4/20014/4/2001 12:00:00 AMPFAIL
tammy ###-#### lead acid battery sign on hallway door; rear door hardware; dampers at shaft; alarm test required with alarm plans; extinguishers require current inspection tags 4/4/2001 3:35:46 PM
BLD98-03628 FIRE-Final Inspection4/4/20014/4/20014/4/2001 12:00:00 AMPPASS
tammy ###-#### structural is also going out today exit to rear of building complete 4/4/2001 3:34:18 PM
BLD00-02308 FIRE-Final Inspection3/28/20014/4/20014/4/2001 12:00:00 AMPPASS
###-####