BLD02-00293
| FIRE-Final Inspection | 4/3/2002 | 4/4/2002 | 4/4/2002 12:00:00 AM | P | FAIL |
|
|
no approved fire sprinkler plans on site, hvac unit did not shut down per umc section 608. No other items were inspected 4/5/2002 9:22:27 AM
|
FIR02-00038
| INSP-Alarm Testing | 4/4/2002 | 4/4/2002 | 4/4/2002 12:00:00 AM | P | FAIL |
|
|
provide corrected zone map at facp panel, provide panel location map for knox box, provide current fire sprinkler riser inspection tag and flow test sprinkler system 1 to verify signal 4/5/2002 10:52:17 AM
|