BLD03-01575
| BLD-Aging Inspection | 4/4/2005 | 4/4/2005 | 4/6/2005 2:59:29 PM | | DONE |
|
|
I called Brian with AIC solutions, ###-####, and left a message on his voice mail requesting status of the fire alarm installation
|
FIR05-00115
| INSP-Final Inspection | 3/31/2005 | 4/4/2005 | 4/4/2005 12:00:07 PM | A | PART |
|
|
Contact: Brian; Phone #: ###-#### Sprinkler rough-in ok to cover in drop ceiling areas. Provide ceilings in rooms without or provide sprinkler protection in areas above.
|
FIR05-00134
| INSP-Final Inspection | 4/1/2005 | 4/4/2005 | 4/4/2005 9:50:43 AM | A | FAIL |
|
|
Duct sampling tubes in two ducts need to be the correct length. Zones at alarm company need to be corrected.
|
FIR04-00627
| INSP-Supply line flush | 4/1/2005 | 4/4/2005 | 4/4/2005 9:00:29 AM | A | FAIL |
|
|
Fail, discharge hose too small to obtain required flow.
|
MIS05-00038
| FIR-Final | 3/31/2005 | 4/4/2005 | 4/1/2005 9:58:56 AM | A | CANC |
|
|
patricia zute or jophn stevens ###-####; Phone #: ###-#### Inspection cancelled, tenant not open on friday's. Actual address is 890N. cole.
|