FIR06-00867
| FIR-Aging Inspection | 4/4/2007 | 4/4/2007 | 4/9/2007 11:28:33 AM | | NR |
|
|
To be scheduled for later date
|
BLD07-00045
| FIRE-Final Inspection | 4/4/2007 | 4/4/2007 | 4/5/2007 8:59:16 AM | P | PASS |
|
|
Life safety passed
|
BLD06-01424
| FIRE-Final Inspection | 4/4/2007 | 4/4/2007 | 4/4/2007 2:06:22 PM | A | FAIL |
|
|
Need the fire alarm and fire sprinkler permits finaled as well as the knox box and signage on the riser room door.
|
FIR07-00152
| INSP-Final Inspection | 4/3/2007 | 4/4/2007 | 4/4/2007 2:04:03 PM | A | FAIL |
|
|
The backflow needs certified and the tamper switches connected to the existing fire alarm panel.
|
FIR07-00152
| INSP-Sprinkler Rough-in/Hydro | 4/3/2007 | 4/4/2007 | 4/4/2007 2:01:17 PM | A | PASS |
|
|
Hydro test and rough-in passed.
|
FIR06-00641
| INSP-Final Inspection | 4/3/2007 | 4/4/2007 | 4/4/2007 10:24:03 AM | A | FAIL |
|
|
need to perform forward flush. trip test of the dry system passed
|
FIR06-00803
| INSP-Final Inspection | 4/3/2007 | 4/4/2007 | 4/4/2007 9:56:09 AM | A | FAIL |
|
|
The smoke detector needs to be relocated to the deck, test the pull station and provide signal report
|