Inspections for the day of: Friday, April 4, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02401 FIRE-Final Inspection4/4/20084/4/20084/4/2008 6:04:21 PMPFAIL
Three messages were left on the phone and a business card left on site but there was no access to the project. No inspection performed.
FIR07-00949 INSP-Sprinkler Rough-in/Hydro4/4/20084/4/20084/4/2008 6:03:08 PMPPASS
Wet system hydro test passed.
FIR08-00198 INSP-Sprinkler Rough-in4/3/20084/4/20084/4/2008 2:23:54 PMAPASS
Sprinkler piping can be covered. One pendant in the restroom is too close to the supply diffuser. Per discussion the fitter is going to relocate it. I will verify this at the final.
FIR08-00036 INSP-Sprinkler Rough-in4/3/20084/4/20084/4/2008 1:53:45 PMPPASS
The remaining underground piping is ok to cover.
BLD06-02968 FIRE-Final Inspection4/1/20084/4/20084/4/2008 1:52:46 PMAFAIL
The four existing emergency lights did not operate. All other items are ok.
FIR07-00505 INSP-Supply line flush4/1/20084/4/20084/4/2008 1:43:42 PMAPASS
Underground flush passed.
BLD05-00633 FIRE-Sprinkler Rough-in4/4/20084/4/20084/4/2008 12:00:00 AMPCANC
carl Phone #: ###-####