Inspections for the day of: Monday, April 4, 2011.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00199 ELE-Aging Inspection4/4/20114/4/20114/6/2011 7:29:07 AM DONE
see final
ELE10-01289 ELE-Aging Inspection4/4/20114/4/20114/6/2011 7:26:56 AM DONE
still under construction, no activity
ELE10-01244 ELE-Aging Inspection4/4/20114/4/20114/5/2011 10:31:06 AM DONE
still under construction
ELE11-00613 Final4/4/20114/4/20114/4/2011 3:10:57 PMPCANC
Phone #: ###-#### >> Inspection requested via web by steve cooper entered twice
ELE11-00614 Electrical Rough-In4/4/20114/4/20114/4/2011 3:10:25 PMPPASS
rough inspection on walls that are open, door should be open, call with questions Don ###-#### Phone #: ###-#### >> Inspection requested via web by Don Lustig open walls and hard lids only ok cover, NOTE: check piping over panels next inspection, called contractor
ELE10-02615 Final4/4/20114/4/20114/4/2011 2:42:15 PMPNH
left card, no contact number
ELE11-00343 Electrical Rough-In4/4/20114/4/20114/4/2011 2:10:17 PMPFAIL
Late afternoon if possible. Electrician Brian ###-#### Phone #: ###-#### >> Inspection requested via web by Dave Koeppen met electrician, NEC 330.30 (B) shall secure cable within 12" of termination since ceiling not accessible
ELE11-00613 Final4/4/20114/4/20114/4/2011 1:13:18 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by steve cooper called, left correction notice, NEC 406.8(B) receptacle shall be listed weather resistasnt type, 250.53(G) upper end of electrode shall be flush with ground, BCC shall post job id sticker, shall post address, fee due
ELE11-00118 Final4/4/20114/4/20114/4/2011 10:22:15 AMAPASS
ok final
ELE11-00606 Rough-In Permanent Service4/2/20114/4/20114/4/2011 10:19:09 AMAPASS
Gararge is open. Phone #: ###-#### >> Inspection requested via web by Steve Ruter ri ok, p/s u/g n ok
ELE10-02615 Electrical Rough-In4/1/20114/4/20114/4/2011 9:13:27 AMAFAIL
Bill Phone #: ###-#### called, no cords and plugs into ceiling
ESC05-01014 DOC - Permit Expired4/4/20114/4/20114/4/2011 8:23:47 AMAPASS
see aging, no address, no sign, no activity