FIR10-00443
| INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 4:11:07 PM | P | CANC |
|
|
Canceled due to time constraints. Rescheduled for tomorrow morning.
|
FIR10-00542
| INSP-Supply line flush | 4/4/2011 | 4/4/2011 | 4/4/2011 4:07:20 PM | P | PASS |
|
|
Underground supply line flush passed.
|
BLD10-00987
| FIRE-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 3:37:18 PM | P | FAIL |
|
|
See the city approved plans for locatins circled in red where exit signs and/or emergency lighting is to be provided per the approved plans. Also see the fire plan review notes for additional requirements such as knox box, building address and door hardware issues.
|
FIR10-00470
| INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 3:31:56 PM | P | PASS |
|
|
permit finaled
|
FIR10-00523
| INSP-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 3:29:59 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00579
| INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 3:29:04 PM | P | PASS |
|
|
permit finaled
|
BLD10-02873
| FIRE-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 3:27:56 PM | P | PASS |
|
|
life safety passed
|
BLD10-02989
| FIRE-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 3:27:27 PM | P | CANC |
|
|
duplicate inspection.
|
BLD10-02989
| FIRE-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 3:26:34 PM | P | FAIL |
|
|
Repair the inoperative exit sign in the break room and repair the inoperative lense in the emergency light in the south vestible.
|
FIR11-00125
| INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 11:32:22 AM | P | CANC |
|
|
Per a phone conversation with Guy this inspection will be rescheduled for tomorrow morning.
|
FIR10-00656
| INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 11:29:40 AM | P | FAIL |
|
|
The last remaining hvac unit in the showroom would not turn on so that automatic shutdown could be tested. The other correction items have been addressed.
|
BLD11-00475
| FIRE-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 11:20:41 AM | P | CANC |
|
|
Jane Phone #: ###-#### Inspection cancelled from web by: Barbara Stitt
|
BLD11-00578
| FIRE-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 10:51:49 AM | A | FAIL |
|
|
Repair the rear corridor exit/emergency light, provide annual inspection for the fire extinguisher and provide single action hardware on one of the main exit doors per the plans or resubmit plans showing a revised square footage.
|
FIR10-00579
| INSP-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 10:02:15 AM | A | PASS |
|
|
Permit finaled
|
BLD10-01234
| FIRE-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 10:00:31 AM | A | FAIL |
|
|
Plans need to be resubmitted showing the wall and door changes in the shop and parts areas which may be increasing the occupant load. Emergency lights need to be installed in the missing locations in the shop and in the oil pit. The project related fire alarm permit needs to be finaled. The changes in the new fire hydrant location is approved by Scott.
|
FIR11-00125
| INSP-Final Inspection | 4/1/2011 | 4/4/2011 | 4/4/2011 8:20:47 AM | A | FAIL |
|
|
No inspection performed. Per Guy this panel still needs the shielded cabling addressed.
|