ELE09-01570
| ELE-Aging Inspection | 4/4/2013 | 4/4/2013 | 4/8/2013 3:08:00 PM | | DONE |
|
|
still under construction
|
ELE12-02163
| Final | 4/4/2013 | 4/4/2013 | 4/5/2013 8:13:10 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Roy Kay Final ok
|
ELE12-02982
| Electrical Rough-In | 4/3/2013 | 4/4/2013 | 4/4/2013 2:21:55 PM | P | PASS |
|
|
tony Phone #: ###-#### Parking garage ceiling pour marked on print. Rough in ok cover
|
ELE13-00171
| Final | 4/4/2013 | 4/4/2013 | 4/4/2013 1:37:25 PM | P | PASS |
|
|
please give me half an hour notice to insure access thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Final ok
|
GCE13-00051
| GCE-Rough-In | 4/3/2013 | 4/4/2013 | 4/4/2013 1:35:44 PM | A | PASS |
|
|
Jerry @ ###-#### Under ground rough in ok cover
|
ELE13-00530
| Final | 4/4/2013 | 4/4/2013 | 4/4/2013 12:52:26 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Detached garage final ok
|
ELE13-00738
| Final | 4/4/2013 | 4/4/2013 | 4/4/2013 12:23:48 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by PAT MILLER Final ok
|
ELE13-00803
| Electrical Rough-In | 4/4/2013 | 4/4/2013 | 4/4/2013 12:02:10 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl Basement cans and outlets rough in ok cover
|
ELE13-00752
| Final | 4/3/2013 | 4/4/2013 | 4/4/2013 11:51:20 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by michael hunt needed permanent service
|
ELE13-00752
| Permanent Service | 4/4/2013 | 4/4/2013 | 4/4/2013 11:50:25 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by michael hunt p/s o/h n ok
|
ELE12-02165
| Final | 4/4/2013 | 4/4/2013 | 4/4/2013 11:28:44 AM | P | CANC |
|
|
Please call 30 minutes before Phone #: ###-#### >> Inspection requested via web by Don Conley Contractor called to inform job not accessible
|
ELE13-00721
| Rough-In Permanent Service | 4/4/2013 | 4/4/2013 | 4/4/2013 11:23:01 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.52- Nook- receptical not located with in 6' of door on right side. 250.96- 3/0 boxes- all metal non current carrying parts shall be bonded. 300.4- bored holes in framing member shall be protected from physical damage by nail plates. Bedroom circuit not complete.
|
ELE13-00770
| Electrical Rough-In | 4/3/2013 | 4/4/2013 | 4/4/2013 10:15:48 AM | A | PASS |
|
|
Contact: Brian Giacomino, underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Underground rough in ok cover
|
GCE13-00048
| GCE-Rough-In | 4/3/2013 | 4/4/2013 | 4/4/2013 9:49:52 AM | A | CANC |
|
|
Henry @ ###-#### Job rescheduled
|
ELE13-00793
| Temporary Service | 4/3/2013 | 4/4/2013 | 4/4/2013 9:30:22 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn 50 amp 240 volt circuit requires GFCI protection
|
GCE13-00050
| GCE-Final | 4/3/2013 | 4/4/2013 | 4/4/2013 9:03:24 AM | A | CANC |
|
|
Jerry @ ###-#### Needed permanent service
|
GCE13-00050
| GCE-Rough-In Permanent Service | 4/4/2013 | 4/4/2013 | 4/4/2013 9:01:34 AM | P | PASS |
|
|
Jerry @ ###-#### Permanent service rough in ok p/s u/g n ok
|
GCE13-00016
| GCE-Final | 4/3/2013 | 4/4/2013 | 4/4/2013 8:38:44 AM | A | PASS |
|
|
David @ ###-#### Final ok
|