Inspections for the day of: Thursday, April 4, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-01875 FIRE-Final Inspection4/4/20134/4/20134/4/2013 3:42:49 PMPPASS
life safety passed
FIR13-00020 INSP-Sprinkler Rough-in4/4/20134/4/20134/4/2013 3:17:57 PMPPASS
See the city approved plans for residence where the rough-in is passed. Tenting has not been completed yet.
BLD13-00122 FIRE-Final Inspection4/3/20134/4/20134/4/2013 2:43:31 PMPPASS
Life safety passed
FIR13-00043 INSP-Sprinkler Rough-in4/3/20134/4/20134/4/2013 2:39:53 PMPPART
Rough-in is ok but need verification that additional fittings in the upper and lower storage room sprinkler system do not adversly effect the hydraulic calculations. Need model number of the air compressor verified for the 4.5 cfm requirement. Need to verify that the backflow preventor is ok (wrong model number). Need approved notes for review. Need storage signage per note #5. As-builts, if time does not require resubmittals, showing the additional piping and heads under both stairways. Also solid shelving has been installed, some of which is 8' x 24'. I contacted Cam and Tim Frost and I'm waiting for an official responce if this shelving is ok.
BLD11-01875 FIRE-Final Inspection4/3/20134/4/20134/4/2013 12:00:16 PMAFAIL
The exit signs still do not work.
BLD13-00652 FIRE-Final Inspection4/3/20134/4/20134/4/2013 9:23:07 AMAPASS
Life safety passed
FIR12-00669 INSP-Final Inspection4/3/20134/4/20134/4/2013 7:39:12 AMAPASS
Permit finaled