BLD11-01875
| FIRE-Final Inspection | 4/4/2013 | 4/4/2013 | 4/4/2013 3:42:49 PM | P | PASS |
|
|
life safety passed
|
FIR13-00020
| INSP-Sprinkler Rough-in | 4/4/2013 | 4/4/2013 | 4/4/2013 3:17:57 PM | P | PASS |
|
|
See the city approved plans for residence where the rough-in is passed. Tenting has not been completed yet.
|
BLD13-00122
| FIRE-Final Inspection | 4/3/2013 | 4/4/2013 | 4/4/2013 2:43:31 PM | P | PASS |
|
|
Life safety passed
|
FIR13-00043
| INSP-Sprinkler Rough-in | 4/3/2013 | 4/4/2013 | 4/4/2013 2:39:53 PM | P | PART |
|
|
Rough-in is ok but need verification that additional fittings in the upper and lower storage room sprinkler system do not adversly effect the hydraulic calculations. Need model number of the air compressor verified for the 4.5 cfm requirement. Need to verify that the backflow preventor is ok (wrong model number). Need approved notes for review. Need storage signage per note #5. As-builts, if time does not require resubmittals, showing the additional piping and heads under both stairways. Also solid shelving has been installed, some of which is 8' x 24'. I contacted Cam and Tim Frost and I'm waiting for an official responce if this shelving is ok.
|
BLD11-01875
| FIRE-Final Inspection | 4/3/2013 | 4/4/2013 | 4/4/2013 12:00:16 PM | A | FAIL |
|
|
The exit signs still do not work.
|
BLD13-00652
| FIRE-Final Inspection | 4/3/2013 | 4/4/2013 | 4/4/2013 9:23:07 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00669
| INSP-Final Inspection | 4/3/2013 | 4/4/2013 | 4/4/2013 7:39:12 AM | A | PASS |
|
|
Permit finaled
|