Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00697 INSP-Sprinkler Rough-in/Hydro4/4/20144/4/20144/4/2014 3:37:02 PMPPASS
Overhead hydro test of the OR area passed.
BLD14-00020 FIRE-Final Inspection4/4/20144/4/20144/4/2014 3:36:14 PMPFAIL
Install and provide testing for all of the exit signs and emergency lights as per the approved plans
FIR14-00126 INSP-Final Inspection4/3/20144/4/20144/4/2014 2:24:44 PMPPASS
Permit finaled
FIR14-00147 INSP-Final Inspection4/3/20144/4/20144/4/2014 2:24:19 PMPPASS
Permit finaled
BLD13-02639 FIRE-Final Inspection4/3/20144/4/20144/4/2014 10:47:35 AMPFAIL
Repair the exit sign and the exit discharge lights. One hvac unit has a duct smoke detector that did not shut down the unit upon activation and does not have the required remote annunciator. Fire extinguishers have been mounted.