Inspections for the day of: Monday, April 4, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00931 Final4/4/20164/4/20164/4/2016 5:15:19 PMPCANC
Phone #: ###-#### Inspection requested via web by Stacie Tasker needed t/s
ELE16-00931 Temporary Service4/4/20164/4/20164/4/2016 5:14:59 PMPFAIL
Phone #: ###-#### Inspection requested via web by Stacie Tasker bond grounded conductor at main only. please leave electricians number so we can call him next time.
ELE15-01617 Conference4/1/20164/4/20164/4/2016 4:24:58 PMPDONE
Ron Hamilton
Phone #: ###-#### Inspection requested via web by Kerri Hamilton discuss data backboard install above xformer on each floor. OK to do this
ELE15-02641 Electrical Rough-In3/31/20164/4/20164/4/2016 3:45:36 PMPPASS
Please call 30 min prior to inspection for access Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok rooms 301, 302 and 303
GCE16-00003 GCE-Rough-In Permanent Service4/4/20164/4/20164/4/2016 2:00:28 PMPFAIL
David ###-#### - requested 30min call ahead p/s not ready 110.24(A)-available fault current label required prior to service energized
GCE16-00003 GCE-Rough-In4/4/20164/4/20164/4/2016 1:58:57 PMPPASS
David ###-#### - requested 30min call ahead r/i walls and ceilings ok
ELE16-01030 Electrical Rough-In4/4/20164/4/20164/4/2016 1:07:14 PMPPASS
Phone #: ###-#### Inspection requested via web by Chris Chesnut r/i walls and ceilings ok
ELE15-00253 Final3/30/20164/4/20164/4/2016 12:09:32 PMAPASS
Inspection requested via web by Greg Traudt corrections made final ok
ELE16-00529 Final4/2/20164/4/20164/4/2016 11:46:48 AMAFAIL
Phone #: ###-#### Inspection requested via web by Stan Woodward 210.62-At least one 120volt receptacle outlet shall be installed within 18" of top of show window for each 12 linear foot (6' or more) of show window. 220.14(G)(2)- 200 va per lineal foot of show window required. 422.31(A) and (B)- disconnect or lockoff on circuit breaker required permanently connected air pump machine
ELE16-01024 Rough-In Permanent Service4/1/20164/4/20164/4/2016 10:37:26 AMAPASS
call jeff for any questions about job @ ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek r/i ok p/s u/g n ok
ELE15-02180 Electrical Rough-In4/1/20164/4/20164/4/2016 9:53:44 AMAPASS
panel and inverter listing inspection
installer will be there from 9:30am to 10:30am, unless you need him to hang out. Just give me a call if that''''s the case.
Thanks guys, Phone #: ###-#### Inspection requested via web by Ryan King r/i ok solar world ul listed array and microprocessor
ELE16-01018 Rough-In Permanent Service4/3/20164/4/20164/4/2016 9:18:39 AMAPASS
Phone #: ###-#### Inspection requested via web by kevin blackmon r/i ok p/s u/g n ok
ELE16-00355 Electrical Rough-In4/1/20164/4/20164/4/2016 8:57:37 AMAPASS
This is for an Underground inspection (not listed as a choice) at the Booster Station. Please Contact Mike TenHulzen with questions. Thank you for your help. Phone #: ###-#### Inspection requested via web by JAMIE WINTERS r/i ok underslab NOTE:jobsite is at the north end of council springs
ELE16-01017 Electrical Rough-In4/1/20164/4/20164/4/2016 12:00:00 AMPCANC
Ron Hamilton
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton
ELE16-01838 Electrical Rough-In4/4/20164/4/20164/4/2016 12:00:00 AMPPASS
Rm 430, 435, 607 Phone #: ###-#### Inspection requested via web by Tom Betty 607 not ready r/i ok 430,435,707 and 708 walls ok