ELE16-00931
| Final | 4/4/2016 | 4/4/2016 | 4/4/2016 5:15:19 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker needed t/s
|
ELE16-00931
| Temporary Service | 4/4/2016 | 4/4/2016 | 4/4/2016 5:14:59 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker bond grounded conductor at main only. please leave electricians number so we can call him next time.
|
ELE15-01617
| Conference | 4/1/2016 | 4/4/2016 | 4/4/2016 4:24:58 PM | P | DONE |
|
|
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton discuss data backboard install above xformer on each floor. OK to do this
|
ELE15-02641
| Electrical Rough-In | 3/31/2016 | 4/4/2016 | 4/4/2016 3:45:36 PM | P | PASS |
|
|
Please call 30 min prior to inspection for access Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok rooms 301, 302 and 303
|
GCE16-00003
| GCE-Rough-In Permanent Service | 4/4/2016 | 4/4/2016 | 4/4/2016 2:00:28 PM | P | FAIL |
|
|
David ###-#### - requested 30min call ahead p/s not ready 110.24(A)-available fault current label required prior to service energized
|
GCE16-00003
| GCE-Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 1:58:57 PM | P | PASS |
|
|
David ###-#### - requested 30min call ahead r/i walls and ceilings ok
|
ELE16-01030
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 1:07:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Chesnut r/i walls and ceilings ok
|
ELE15-00253
| Final | 3/30/2016 | 4/4/2016 | 4/4/2016 12:09:32 PM | A | PASS |
|
|
Inspection requested via web by Greg Traudt corrections made final ok
|
ELE16-00529
| Final | 4/2/2016 | 4/4/2016 | 4/4/2016 11:46:48 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Stan Woodward 210.62-At least one 120volt receptacle outlet shall be installed within 18" of top of show window for each 12 linear foot (6' or more) of show window. 220.14(G)(2)- 200 va per lineal foot of show window required. 422.31(A) and (B)- disconnect or lockoff on circuit breaker required permanently connected air pump machine
|
ELE16-01024
| Rough-In Permanent Service | 4/1/2016 | 4/4/2016 | 4/4/2016 10:37:26 AM | A | PASS |
|
|
call jeff for any questions about job @ ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek r/i ok p/s u/g n ok
|
ELE15-02180
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 9:53:44 AM | A | PASS |
|
|
panel and inverter listing inspection installer will be there from 9:30am to 10:30am, unless you need him to hang out. Just give me a call if that''''s the case. Thanks guys, Phone #: ###-#### Inspection requested via web by Ryan King r/i ok solar world ul listed array and microprocessor
|
ELE16-01018
| Rough-In Permanent Service | 4/3/2016 | 4/4/2016 | 4/4/2016 9:18:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon r/i ok p/s u/g n ok
|
ELE16-00355
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 8:57:37 AM | A | PASS |
|
|
This is for an Underground inspection (not listed as a choice) at the Booster Station. Please Contact Mike TenHulzen with questions. Thank you for your help. Phone #: ###-#### Inspection requested via web by JAMIE WINTERS r/i ok underslab NOTE:jobsite is at the north end of council springs
|
ELE16-01017
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 12:00:00 AM | P | CANC |
|
|
Ron Hamilton Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton
|
ELE16-01838
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 12:00:00 AM | P | PASS |
|
|
Rm 430, 435, 607 Phone #: ###-#### Inspection requested via web by Tom Betty 607 not ready r/i ok 430,435,707 and 708 walls ok
|