ELE16-00329
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 3:22:02 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 2nd floor hard lid cielings in corridor ok cover
|
ELE16-00891
| Temporary Service | 4/3/2016 | 4/4/2016 | 4/4/2016 2:54:47 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
|
ELE16-00056
| Final | 4/4/2016 | 4/4/2016 | 4/4/2016 2:48:35 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 410.11(d) luminares located with 8' of a shower or bathtub shall be marked for damp locations as well as the lamp shall be suitable for such use 422.31 permamanetly insatlled appliances shall have means of lockout
|
ESC15-01294
| Site Final | 4/4/2016 | 4/4/2016 | 4/4/2016 2:25:43 PM | P | PASS |
|
|
site final ok
|
ELE15-00629
| Final | 4/4/2016 | 4/4/2016 | 4/4/2016 2:06:34 PM | P | PASS |
|
|
Please call ahead for access - Annie Phone #: ###-#### corrections fixed final ok
|
ELE16-00912
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 2:05:53 PM | P | PASS |
|
|
Gate open, dog in house. When digging for foundation, I broke the electrical wire that went to my detached garage...which was just a romex wire buried in the ground. Installed a sub panel on garage. Would like to bury. Thanx, JIm Phone #: ###-#### Inspection requested via web by James Friedrich underground ok cover
|
ELE16-00912
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 2:05:47 PM | P | FAIL |
|
|
Gate open, dog in house. When digging for foundation, I broke the electrical wire that went to my detached garage...which was just a romex wire buried in the ground. Installed a sub panel on garage. Would like to bury. Thanx, JIm Phone #: ###-#### Inspection requested via web by James Friedrich 230.72 service disconnecting means is required for seperate services 250.23 grounding electrode system required for seperate services 334.12 type NM cable shall not be used in a wet location 408.36(d) back fed devices shall be secured in place by a listed fastener
|
ELE16-01025
| Conference | 4/1/2016 | 4/4/2016 | 4/4/2016 1:27:03 PM | P | DONE |
|
|
Thomas// please call before Phone #: ###-#### discussed refeading shop using existing wire from old shop location and NEC requirements for GFCI protecion in shop and grouding requirements
|
ELE16-01005
| Final | 4/4/2016 | 4/4/2016 | 4/4/2016 12:28:32 PM | P | PASS |
|
|
Greg Phone #: ###-#### correction fixed final ok
|
ELE16-00904
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 12:23:19 PM | P | PASS |
|
|
Trench inspection Phone #: ###-#### Inspection requested via web by steve sellers underground fro detached garage to house ok cover
|
ELE15-04115
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 11:06:01 AM | A | PASS |
|
|
Call when in route if possible; obtain visitors badge from front desk Phone #: ###-#### Inspection requested via web by Steve McCloy offices and conference rooms cieling only ok cover
|
ELE15-03833
| Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 10:07:07 AM | A | PASS |
|
|
floor heat inspection master bathroom Phone #: ###-#### Inspection requested via web by steve sellers master bath floor heat ok cover
|
ELE16-00782
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 9:47:42 AM | A | PASS |
|
|
Potting ; Equal Potential Inspection Phone #: ###-#### Inspection requested via web by Louis Keller pool lighting potting and equipotential bonding ok cover
|
ELE16-00170
| Final | 4/4/2016 | 4/4/2016 | 4/4/2016 9:25:07 AM | P | PASS |
|
|
ready now. code Phone #: ###-#### Inspection requested via web by Bob Glenn corrections fixed final ok
|
ELE16-00012
| Final | 4/4/2016 | 4/4/2016 | 4/4/2016 9:14:58 AM | A | PASS |
|
|
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
|
ELE16-01023
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 8:56:35 AM | A | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by TOM BICANDI underground ok cover
|
ELE16-01022
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 8:56:07 AM | A | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by TOM BICANDI underground ok cover
|
ELE16-01021
| Electrical Rough-In | 4/1/2016 | 4/4/2016 | 4/4/2016 8:55:24 AM | A | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by TOM BICANDI underground ok cover
|
ELE16-00851
| Final | 4/2/2016 | 4/4/2016 | 4/2/2016 10:58:48 AM | A | CANC |
|
|
Side gate and garage man door are open Phone #: ###-#### >> Inspection requested via web by Jarod Murray Inspection cancelled from web by: Jarod Murray
|
ELE16-00945
| Final | 4/2/2016 | 4/4/2016 | 4/2/2016 10:58:08 AM | A | CANC |
|
|
Back gate and side door to garage are open Phone #: ###-#### >> Inspection requested via web by Jarod Murray Inspection cancelled from web by: Jarod Murray
|