BLD99-01412
| FIRE-Final Inspection | 4/5/2000 | 4/5/2000 | 4/11/2000 12:00:00 AM | P | PASS |
|
|
###-#### PLEASE CALL MARK FIRST BEFORE YOU GO,.- per Perry all okay for final
|
BLD99-03739
| FIRE-Final Inspection | 4/3/2000 | 4/5/2000 | 4/5/2000 12:00:00 AM | A | FAIL |
|
|
don ###-#### fn----fire Inspection cancelled, not ready 4/6/00 8:49:32 AM
|
BLD99-03342
| FIRE-Final Inspection | 4/4/2000 | 4/5/2000 | 4/5/2000 12:00:00 AM | A | FAIL |
|
|
Kim Hutchings ###-#### please call before you go out Final fail c/n issued 4/6/00 8:50:39 AM
|
BLD00-00236
| FIRE-Final Inspection | 4/4/2000 | 4/5/2000 | 4/5/2000 12:00:00 AM | A | PASS |
|
|
###-#### Paul Final ok for perm. occ. or letter of completeion 4/6/00 8:50:27 AM
|
FIR00-00015
| INSP-Sprinkler Rough-in/Hydro | 4/4/2000 | 4/5/2000 | 4/5/2000 12:00:00 AM | P | FAIL |
|
|
###-#### *JWA* Lines/heads both in the basement and main level are overspaced for system design spacing. Lack coverage in some partition "coves". Main floor line sprinklers on the south side are all below 6" from bottom of joists or 18" from roof deck maximum allowance. Heads overspaced (120 sq ft. per head) under east entry (basement).
|
BLD00-00250
| FIRE-Sprinkler Rough-in | 4/4/2000 | 4/5/2000 | 4/4/2000 12:00:00 AM | P | PASS |
|
|
Gary Oliver ###-#### okay to cover
|