ELE04-00907
| Rough-In Permanent Service | 4/2/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | A | PASS |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Darla Downs
rough ok 4/5/2004 10:12:02 AM
|
ELE04-00859
| Temporary Service | 4/2/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | A | PASS |
|
|
troy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
t/s u/g n ok
4/5/2004 11:30:41 AM
|
ELE04-00937
| Electrical Rough-In | 4/2/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | A | PASS |
|
|
###-#### joe
rough ok 4/5/2004 11:48:33 AM
|
ELE04-00247
| Final | 4/2/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | A | PASS |
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
210.8B gfi recep survey item 4/5/2004 11:09:25 AM
|
ELE04-00670
| Electrical Rough-In | 4/2/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | A | PART |
|
|
eupher ground///troy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
eupher ok 4/5/2004 10:46:45 AM
|
ELE04-00247
| Final | 4/5/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | A | PASS |
|
|
sent per bill thomaa
final ok survey 210.8b 4/5/2004 11:21:15 AM
|
ELE04-00899
| Final | 4/5/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | P | PASS |
|
|
harvey; Phone #: ###-#### Internet Inspection Request from: Annette Moore
final ok 4/5/2004 3:39:52 PM
|
ELE04-00890
| Permanent Service | 4/5/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | P | FAIL |
|
|
ext 4753 please call for access info///jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
250.52A3 ufer needed 4/5/2004 1:29:41 PM
|
ELE04-00484
| Electrical Rough-In | 4/5/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | P | FAIL |
|
|
ceiling cover///dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
300.11 cieling grid wires shall not be used as support. 4/5/2004 4:35:03 PM
|
ELE04-00182
| Final | 4/5/2004 | 4/5/2004 | 4/5/2004 12:00:00 AM | P | FAIL |
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Darla Downs
250.52 grounding electrode(water piping), 250.104 bonding junper(water heater), 250.24 isolate neutral/grounds(sub panel), 358.22 emt conductor fill(ac 1/2" conduit) 4/5/2004 10:02:27 PM
|