Inspections for the day of: Monday, April 5, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00907 Rough-In Permanent Service4/2/20044/5/20044/5/2004 12:00:00 AMAPASS
dave; Phone #: ###-#### Internet Inspection Request from: Darla Downs
rough ok 4/5/2004 10:12:02 AM
ELE04-00859 Temporary Service4/2/20044/5/20044/5/2004 12:00:00 AMAPASS
troy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
t/s u/g n ok
4/5/2004 11:30:41 AM
ELE04-00937 Electrical Rough-In4/2/20044/5/20044/5/2004 12:00:00 AMAPASS
###-#### joe
rough ok 4/5/2004 11:48:33 AM
ELE04-00247 Final4/2/20044/5/20044/5/2004 12:00:00 AMAPASS
MIKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
210.8B gfi recep survey item 4/5/2004 11:09:25 AM
ELE04-00670 Electrical Rough-In4/2/20044/5/20044/5/2004 12:00:00 AMAPART
eupher ground///troy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
eupher ok 4/5/2004 10:46:45 AM
ELE04-00247 Final4/5/20044/5/20044/5/2004 12:00:00 AMAPASS
sent per bill thomaa
final ok survey 210.8b 4/5/2004 11:21:15 AM
ELE04-00899 Final4/5/20044/5/20044/5/2004 12:00:00 AMPPASS
harvey; Phone #: ###-#### Internet Inspection Request from: Annette Moore
final ok 4/5/2004 3:39:52 PM
ELE04-00890 Permanent Service4/5/20044/5/20044/5/2004 12:00:00 AMPFAIL
ext 4753 please call for access info///jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
250.52A3 ufer needed 4/5/2004 1:29:41 PM
ELE04-00484 Electrical Rough-In4/5/20044/5/20044/5/2004 12:00:00 AMPFAIL
ceiling cover///dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
300.11 cieling grid wires shall not be used as support. 4/5/2004 4:35:03 PM
ELE04-00182 Final4/5/20044/5/20044/5/2004 12:00:00 AMPFAIL
joe; Phone #: ###-#### Internet Inspection Request from: Darla Downs
250.52 grounding electrode(water piping), 250.104 bonding junper(water heater), 250.24 isolate neutral/grounds(sub panel), 358.22 emt conductor fill(ac 1/2" conduit) 4/5/2004 10:02:27 PM