Inspections for the day of: Tuesday, April 5, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-04102 Electrical Rough-In4/4/20054/5/20054/5/2005 12:00:00 AMAPASS
carol ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 4/5/2005 9:55:18 AM
ELE05-01114 Temporary Service4/4/20054/5/20054/5/2005 12:00:00 AMAPASS
t/p zane ###-#### t/s u/g new ok 4/5/2005 8:07:59 AM
ELE05-01115 Temporary Service4/4/20054/5/20054/5/2005 12:00:00 AMAPASS
###-####--zane t/s u/g new ok 4/5/2005 8:08:15 AM
ELE04-03437 Electrical Rough-In4/4/20054/5/20054/5/2005 12:00:00 AMAFAIL
DAN CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy cor. posted called 300.11 ID wires that support cables, install them from grid to strusture , 210.62 show window outlets 4/5/2005 8:59:58 AM
ELE05-00459 Electrical Rough-In4/4/20054/5/20054/5/2005 12:00:00 AMAFAIL
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called 210.52(A),(B),(D) required outlets for wall space, only what code allows on small appliance brach circuits, all recepts in M bath shall be on bath 20 amp, 300.4(A)(1)&(D) nail plates and 11/4", 314.16 box fill notice for owner 300.4 nail plates and 11/4" bushings for cables, connectors for ENT reinspection fee due 4/5/2005 10:55:07 AM
ELE05-00867 Electrical Rough-In4/5/20054/5/20054/5/2005 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 4/5/2005 at 7:01:25 AM. Contact: ###-####. walls durg area 4/5/2005 11:08:43 AM
ELE05-01128 Final4/5/20054/5/20054/5/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok correction posted for owner BCC no violations to be retained, 300.3 wiring feeding shop shall be in raceay, or approved cabled , single conductors not allowed talked with owner 4/5/2005 12:40:19 PM
ELE05-01131 Electrical Rough-In4/5/20054/5/20054/5/2005 12:00:00 AMPFAIL
###-#### - clyde cor. posted called dinning rm shall be wired on small appliance branch circuit, note u/g for post light not inspected, and plans shall be at job site 4/5/2005 3:38:24 PM
ELE04-03427 Final4/5/20054/5/20054/5/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 4/5/2005 at 10:07:02 AM. Contact: ###-####. ok card signed 4/5/2005 2:35:38 PM
ELE05-01137 Final4/5/20054/5/20054/5/2005 12:00:00 AMPFAIL
amy ###-#### or homeowner at mel campbell ###-#### cor. posted called r/i not final, 300.5 pvc shall be 18", 680.21 wiring from spa disconnet to spa shall have insulated equip grd, 680.22(A)(3) recept between 10&20ft, 680.28 bonding not done , 680.22(B)(3) check existing fixture for clearence note spa not there yet 4/5/2005 3:07:19 PM