Inspections for the day of: Thursday, April 5, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00592 Rough-In Permanent Service4/5/20074/5/20074/5/2007 3:44:31 PMPFAIL
Let me know if this doesn''t pass! Thank you!
Phone #: ###-#### met contr, left corr notice, nec 250.52(A)(3) & BCC new construction shall have concrete encased electrode, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 110.12(C) there shall be no damaged cable, BCC all u/g shall be inspected before cover, approved set of plans shall be on job
ELE07-00594 Rough-In Permanent Service4/5/20074/5/20074/5/2007 3:43:38 PMPFAIL
If you are in the Rose Hill area before noon rowhouses are ready. I just didn''t get on the inspection request time before 7:30 to request them. Thanks Mike! Phone #: ###-#### met contr, left corr notice, nec 250.52(A)(3)&BCC new construction shall have concrete encased electrode, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC all u/g shall be inspected before cover, approved plans shall be on job, address shall be posted
ELE07-00874 Electrical Rough-In4/5/20074/5/20074/5/2007 2:23:55 PMPPASS
bryan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok, talked about room count on permit, contr will call and fix, NOTE :garage not done yet
ELE07-00846 Electrical Rough-In4/5/20074/5/20074/5/2007 1:31:49 PMPPART
Request electrical rough in for new breakroom/bathrooms in main building Phone #: ###-#### walls only, break room, walls and hard lids baths (2) ok to cover
ELE06-03905 Final4/5/20074/5/20074/5/2007 1:19:28 PMPPASS
H G ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok to final
ELE06-03537 Final4/4/20074/5/20074/5/2007 12:31:40 PMPPASS
Scheduled by a contractor via Hello! on 4/4/2007 at 9:19:09 PM. Contact: ###-####. ok to final
ELE07-01134 Electrical Rough-In4/5/20074/5/20074/5/2007 11:01:01 AMAPASS
One new wall inside Phone #: ###-#### wall only ok to cover
ELE06-02896 Final4/3/20074/5/20074/5/2007 10:59:02 AMAPART
jerri; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walked with elect left list such as labels, warning signs,ground gen set, FACP does not have proper clearance, pole lights need ground lugs, lights, recpts ok, they are working on owner's punch list
ELE07-00791 Electrical Rough-In4/4/20074/5/20074/5/2007 9:38:37 AMACANC
duane Note: new box power line; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong type inspection, see p/s
ELE07-00791 Permanent Service4/5/20074/5/20074/5/2007 9:37:50 AMAPASS
duane Note: new box power line; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec ok
ELE07-00449 Permanent Service4/4/20074/5/20074/5/2007 9:21:33 AMAPASS
rocky Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles correction made, p/s, o/h, rec, ok
ELE07-00076 Final4/4/20074/5/20074/5/2007 8:53:42 AMAPASS
the key is under the can on the meter main Phone #: ###-#### corr made, ok to final
ELE07-01129 Rough-In Permanent Service4/4/20074/5/20074/5/2007 8:08:33 AMAPASS
Brandon ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ric ok, p/s u/g n ok
ELE06-02392 Conference4/4/20074/5/20074/4/2007 5:42:22 PMPCANC
please call Randy and meet him on project to discuss issues with electrical. around 2:30 would be great if possible. If no answer call Loren at ###-#### Phone #: ###-#### Inspection cancelled from web by: Loren Ramsey