FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 4/4/2007 | 4/5/2007 | 4/5/2007 5:57:59 PM | P | PART |
|
|
OH fire sprinkler install at the 5th floor NE quadrant is acceptable for cover, noted one head in an OTS telephone room to be raised closer to the deck for proper heat collection, two arm overs at the restrooms to have hangers within 1' of the pendent head, seismic bracing 80% complete, the OH hydrostatic test is satisfactory.
|
MIS07-00024
| FIR-Final | 4/5/2007 | 4/5/2007 | 4/5/2007 5:53:31 PM | P | PASS |
|
|
Items on the issued correction notice have been completed, life safety finaled.
|
MIS07-00008
| FIR-Final | 4/4/2007 | 4/5/2007 | 4/5/2007 5:52:10 PM | A | PASS |
|
|
Life safety inspection passed, noted the provided PFE to be lowered to a max. height of 48" AFF as discussed.
|
FIR07-00092
| INSP-Final Inspection | 4/5/2007 | 4/5/2007 | 4/5/2007 3:00:06 PM | P | PASS |
|
|
OH fire sprinkler final passed inspection.
|
BLD06-00653
| FIRE-Final Inspection | 4/4/2007 | 4/5/2007 | 4/5/2007 2:58:25 PM | A | FAIL |
|
|
Missing fire extinguisher, manual thumbturns are not allowed at egress doors, the project related fire alarm permit must be issued, inspected, and finaled prior to bld life safety final.
|
FIR07-00218
| INSP-Final Inspection | 4/5/2007 | 4/5/2007 | 4/5/2007 2:31:51 PM | P | PASS |
|
|
Final fire sprinkler inspection passed, permit finaled.
|
BLD05-02392
| FIRE-Final Inspection | 4/4/2007 | 4/5/2007 | 4/5/2007 2:30:37 PM | A | PASS |
|
|
Items in need of correction have been completed, final fire life safety inspection passed.
|
FIR06-00728
| INSP-Sprinkler Rough-in/Hydro | 4/4/2007 | 4/5/2007 | 4/5/2007 2:29:05 PM | A | DONE |
|
|
Air test concluded.
|
FIR07-00241
| INSP-Final Inspection | 4/4/2007 | 4/5/2007 | 4/5/2007 10:15:15 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|