Inspections for the day of: Monday, April 5, 2010.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00222 Final4/5/20104/5/20104/5/2010 4:04:05 PMPPASS
ed Phone #: ###-#### ok to final
ELE10-00221 Final4/5/20104/5/20104/5/2010 3:39:12 PMPPASS
ed Phone #: ###-#### ok to final
ESC09-00511 General Inspection4/5/20104/5/20104/5/2010 3:30:24 PMPPASS
ESC09-00510 General Inspection4/5/20104/5/20104/5/2010 3:29:49 PMPPASS
ESC10-00013 General Inspection4/5/20104/5/20104/5/2010 3:29:06 PMPPASS
ESC09-00509 General Inspection4/5/20104/5/20104/5/2010 3:28:29 PMPPASS
ESC09-00742 General Inspection4/5/20104/5/20104/5/2010 3:27:55 PMPPASS
ELE10-00021 Final4/5/20104/5/20104/5/2010 3:23:13 PMPPASS
Angel ###-#### ok to final, no esc this project
ELE10-00401 Final4/5/20104/5/20104/5/2010 3:11:04 PMPPASS
Gene Phone #: ###-#### ok to final, no esc this project
ELE10-00686 Final4/5/20104/5/20104/5/2010 2:34:49 PMPPASS
wired in ansel system on hood range Inspection requested from web by: cory carman Phone #: ###-#### ok to final, signed occupancy card, no esc this project
ELE10-00685 Rough-In Permanent Service4/5/20104/5/20104/5/2010 1:49:37 PMPCANC
please call 1/2 hr prior//Dave ###-####see ri and p/s
ELE10-00685 Permanent Service4/5/20104/5/20104/5/2010 1:44:38 PMPPASS
please call 1/2 hr prior//Dave ###-#### p/s u/g n ok
ELE10-00685 Electrical Rough-In4/5/20104/5/20104/5/2010 1:24:08 PMPFAIL
please call 1/2 hr prior//Dave ###-#### called, left correction notice, NEC
314.17(C) shall secure nm cable within 8" of box, #12 and #8, 210.52(C) shall provide receptacle within 2' of sink or in 2' wall space, BCC shall not cover any wiring before inspection, entry, walls, shall add 1 room to permit, NOTE corrections shall be made within 5 working days or further action may be taken
ELE10-00179 Final4/5/20104/5/20104/5/2010 12:58:34 PMPPASS
ed Phone #: ###-#### ok to final
ELE09-01602 Final4/5/20104/5/20104/5/2010 11:20:26 AMPCANC
Final Inspect. No one is on site, so please call ###-#### one hour prior to arrival and we will meet you there. Contact is Brian Cornell. Inspection requested from web by: Richard Montgomery Phone #: ###-#### Inspection cancelled from web by: Richard Montgomery
ELE10-00286 Final4/5/20104/5/20104/5/2010 9:52:15 AMAFAIL
###-#### Inspection requested from web by: Todd Holbrook called, left correction notice, NEC 250.94 shall provide intersystem bonding bar, 408.4 shall provide clear and concise circuit directory, 210.8(A)(3) front outdoor receptacle shall be gfci protected, 210.52 shall provide receptacle along bar, BCC all receptacles shall operate-garage, NOTE corrections shall be made in 5 working days or further action will be taken, such as removal of power
ELE10-00663 Electrical Rough-In4/2/20104/5/20104/5/2010 9:00:32 AMACANC
Contact Paul Cushing Inspection requested from web by: Shelli Daylong Phone #: ###-#### called contractor, owner sleeps till pm, will recall
ELE10-00680 Electrical Rough-In4/2/20104/5/20104/5/2010 8:25:33 AMAPASS
Uffer, and sleeves. Early inspection please if possible. Inspection requested from web by: Mark Sessions Phone #: ###-#### grounding electrode and conductor, sleeves ok to cover