Inspections for the day of: Thursday, April 5, 2012.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00503 FIR-Aging Inspection4/5/20124/5/20124/9/2012 3:55:43 PM DONE
Was notified by the fire alarm plan reviewer that she has been contacted by an engineer about design issues for the school.
BLD12-00481 FIRE-Final Inspection4/4/20124/5/20124/5/2012 3:42:37 PMPPART
A temporary occupancy was given until the sprinkler pendant issue is addressed. Currently two pendants are located too close to one another due to a soffit that has been removed.
BLD12-00522 FIRE-Final Inspection4/5/20124/5/20124/5/2012 3:37:31 PMPPASS
life safety passed
FIR12-00148 INSP-Final Inspection4/5/20124/5/20124/5/2012 3:08:12 PMPFAIL
Monitoring had not been set up, manual pull station was mounted too high, wall PIV tamper switch was not set correctly. No actual testing was performed. Steve was going to pre-test and reschedule for the morning. Also this FIR permit is attached to the wrong BLD.
BLD12-00668 FIRE-Final Inspection4/5/20124/5/20124/5/2012 1:29:12 PMPPASS
life safety passed
FIR11-00607 INSP-Sprinkler Rough-in/Hydro4/4/20124/5/20124/5/2012 1:22:56 PMAPASS
Overhead hydro test passed
FIR11-00574 INSP-Final Inspection4/4/20124/5/20124/5/2012 11:29:44 AMACANC
Cancel per Randy since the monitoring information has not been set up.