ELE09-01766
| ELE-Aging Inspection | 4/5/2013 | 4/5/2013 | 4/5/2013 3:07:41 PM | | DONE |
|
|
still under construction
|
ELE09-01975
| ELE-Aging Inspection | 4/5/2013 | 4/5/2013 | 4/5/2013 3:03:33 PM | | DONE |
|
|
still under construction
|
ELE09-01904
| ELE-Aging Inspection | 4/5/2013 | 4/5/2013 | 4/5/2013 3:02:30 PM | | DONE |
|
|
still under construction
|
ELE13-00358
| Final | 4/4/2013 | 4/5/2013 | 4/5/2013 2:45:13 PM | P | PASS |
|
|
Contact is Phil Keetch ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok final
|
ELE13-00808
| Permanent Service | 4/4/2013 | 4/5/2013 | 4/5/2013 2:11:58 PM | P | FAIL |
|
|
For access, please call Nick at ###-####, thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan called, shall provide 8' clearance for service conductors, remove low voltage system from mast, per NEC 230, shall provide means to ensure center of breaker handle not over 6'-7" per NEC 240
|
ELE13-00024
| Final | 4/5/2013 | 4/5/2013 | 4/5/2013 1:38:12 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections mqade, ok final
|
ELE12-02372
| Final | 4/5/2013 | 4/5/2013 | 4/5/2013 1:04:01 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Chesnut called, shall label panels with circuit directory, shall install 50 per cent energy efficient bulbs, shall repair gfci in laundry room[
|
ELE13-00786
| Final | 4/5/2013 | 4/5/2013 | 4/5/2013 12:17:07 PM | P | PASS |
|
|
IF NEEDING INSIDE THE HOUSE YOU CAN CALL KEVIN KELLY BEFORE INSPECTION TO MAKE SURE HE IS HOME. ###-#### Phone #: ###-#### >> Inspection requested via web by Eric Chaffin ok final
|
ELE13-00027
| Final | 4/4/2013 | 4/5/2013 | 4/5/2013 10:22:48 AM | A | PASS |
|
|
Bob, this is my blanket permit for Building 24 work orders. Phone #: ###-#### >> Inspection requested via web by Eric Landberg ok final
|
ELE13-00028
| Final | 4/4/2013 | 4/5/2013 | 4/5/2013 10:21:33 AM | A | PASS |
|
|
Bob, this is my blanket permit for clean room tool installs in Building 24. Phone #: ###-#### >> Inspection requested via web by Eric Landberg ok final
|
ELE13-00753
| Rough-In Permanent Service | 4/5/2013 | 4/5/2013 | 4/5/2013 10:19:24 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk see ri
|
ELE13-00753
| Electrical Rough-In | 4/5/2013 | 4/5/2013 | 4/5/2013 10:19:03 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, ri ok
|
ELE13-00679
| Rough-In Permanent Service | 4/4/2013 | 4/5/2013 | 4/5/2013 10:16:58 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE13-00726
| Rough-In Permanent Service | 4/4/2013 | 4/5/2013 | 4/5/2013 10:14:08 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE12-00321
| Electrical Rough-In | 4/4/2013 | 4/5/2013 | 4/5/2013 10:12:13 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk see ri
|
ELE12-02372
| Final | 4/4/2013 | 4/5/2013 | 4/5/2013 10:11:23 AM | A | NR |
|
|
Final. CJ is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut told electrician to call when done, fee due
|
ELE13-00753
| Electrical Rough-In | 4/5/2013 | 4/5/2013 | 4/5/2013 10:08:29 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, ri ok
|
ELE13-00682
| Final | 4/5/2013 | 4/5/2013 | 4/5/2013 8:42:06 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson see ri, p/s
|
ELE13-00682
| Rough-In Permanent Service | 4/5/2013 | 4/5/2013 | 4/5/2013 8:41:36 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ri ok, p/s u/g n ok
|
ELE13-00024
| Final | 4/3/2013 | 4/5/2013 | 4/5/2013 8:21:33 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins shall add 2 rooms to permit, switch plate, shall label panels clearly and legibly to identify circuits, shall provide gfci protection for garage receptacles, owner moved in, could not access all receptacles, shall install fixtures in garage and ensure they operate, shall safe off front light and low wiring below fixture, no address posted
|
ELE13-00743
| Final | 4/4/2013 | 4/5/2013 | 4/4/2013 4:27:04 PM | P | CANC |
|
|
Margaret is the homeowner and a school teacher, she does not get home until 4:00pm. This was a upgrade of knob/tube wiring (2nd phase). Please call Brad @ alloway elec, ###-#### if any questions. Phone #: ###-#### >> Inspection requested via web by brad williams Inspection cancelled from web by: brad williams
|