Inspections for the day of: Tuesday, April 5, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00536 Permanent Service4/5/20164/5/20164/5/2016 3:01:24 PMPFAIL
Call half hour before // Larry Phone #: ###-####
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that is available at the line terminals of the equipment. 10K installed 22K needed
ELE16-00303 Electrical Rough-In4/5/20164/5/20164/5/2016 2:24:05 PMPPASS
Wall cover inspection 3rd floor Phone #: ###-#### Inspection requested via web by Toby Groves
Walls marked in green only rough in ok cover
ELE16-00904 Electrical Rough-In4/5/20164/5/20164/5/2016 12:57:18 PMPPASS
floor heat inspection in master bathroom Phone #: ###-#### Inspection requested via web by steve sellers
Floor heat rough in ok cover
ELE16-01003 Final4/4/20164/5/20164/5/2016 11:24:41 AMAFAIL
Please call Dan Mitchell at ###-#### about 20 to 30 minutes before you arrive and he will meet you on site. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell See permanent service
ELE16-01003 Permanent Service4/4/20164/5/20164/5/2016 11:23:04 AMAFAIL
Please call Dan Mitchell at ###-#### about 20 to 30 minutes before you arrive and he will meet you on site. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell
230.95(C)- For services above 150 volts to ground but less than 1000 volts phase to phase overcurrent devices shall be performance tested when first set on site.
250.24- Unable to verify main bonding jumper to bond neutral.
ELE16-01003 Electrical Rough-In4/4/20164/5/20164/5/2016 11:00:49 AMAFAIL
Please call Dan Mitchell at ###-#### about 20 to 30 minutes before you arrive and he will meet you on site. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell
See permanent service notes.
ELE16-01053 Electrical Rough-In4/4/20164/5/20164/5/2016 10:40:01 AMAPASS
Contractor will have someone on site by 9am. Homeowner should be home till 9am please call if inspection will be before 9am to confirm homeowner is still home. Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
Kitchen, laundry, and lighting in nook, living, bar rough in ok cover.
ELE16-00997 Rough-In Permanent Service4/4/20164/5/20164/5/2016 10:20:40 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
Rough in ok cover p/s u/g n ok
ELE16-01035 Temporary Service4/4/20164/5/20164/5/2016 9:50:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
t/s u/g n ok
ELE16-01044 Electrical Rough-In4/4/20164/5/20164/5/2016 9:17:45 AMAPASS
Please inspect patio to room remodel. Phone #: ###-#### Inspection requested via web by ERIC CENTERS
Walls and ceiling rough in ok cover
ELE16-01033 Rough-In Permanent Service4/4/20164/5/20164/5/2016 8:36:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok