BLD16-01265
| FIRE-Final Inspection | 4/5/2017 | 4/5/2017 | 4/5/2017 4:13:47 PM | P | PASS |
|
|
Exit lights have been changed to weather proof fixtures. Final life fire safety inspection passed/complete.
|
FIR17-00097
| INSP-Sprinkler Rough-in | 4/5/2017 | 4/5/2017 | 4/5/2017 12:18:11 PM | P | PART |
|
|
Rough in inspection complete for wet system, tenting will be installed at a later date, notated city approved drawings with pink highlighter/red ink area's inspected. Partial inspection copleted on attic dry system, notated city approved drawings with pink highlighter/red ink area's on dry system approved for cover.
|
FIR16-00607
| INSP-Sprinkler Rough-in | 4/5/2017 | 4/5/2017 | 4/5/2017 11:15:33 AM | P | FAIL |
|
|
Tenting is not complete, no insulation installed over piping in numerous area's. City approved drawings show a detail with attic space being completely filled with insulation, numerous area's have 6 plus inches of combustible material exposed, insulation needs to fill any and all area's in attic space or upright head protection will be required, refer to note number 8 of fire sprinkler permit review comments for specifics.
|
FIR16-00606
| INSP-Sprinkler Rough-in | 4/5/2017 | 4/5/2017 | 4/5/2017 11:10:26 AM | P | CANC |
|
|
Incorrect permit for inspection request, (Inspection request is for tenting associated with FIR16-00607, building 3 clubhouse) this request is cancelled and an inspection request will be generated for the correct permit number.
|
FIR17-00139
| INSP-Sprinkler Rough-in | 4/4/2017 | 4/5/2017 | 4/5/2017 8:12:27 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hard lid area's complete, approved for cover.
|
FIR17-00112
| INSP-Sprinkler Rough-in | 4/5/2017 | 4/5/2017 | 4/5/2017 12:00:00 AM | P | CANC |
|
|
Ok to cover // Don Phone #: ###-####-Don called and said he needed to cancel this inspection
|