MEC19-01382
| Rough-in | 4/4/2019 | 4/5/2019 | 4/5/2019 4:16:55 PM | P | FAIL |
|
|
lock box 1027 Phone #: ###-#### Inspection requested via web by Joseph Profitt - Exhaust fan ducting needs sealed - exhaust fan flex size doesn't match the prints - supply run into the nitrous storage needs sealed - need to see outside air ducts for all WSHP's installed
|
MEC18-06094
| Final | 4/5/2019 | 4/5/2019 | 4/5/2019 3:34:36 PM | P | PASS |
|
|
home owner will be home after 2 pm Phone #: ###-#### Inspection requested via web by thomas nguyen - CO's ok - final ok
|
MEC19-01367
| Final | 4/4/2019 | 4/5/2019 | 4/5/2019 2:38:56 PM | P | PASS |
|
|
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - A/C coil co ok
|
MEC19-00603
| Final | 4/4/2019 | 4/5/2019 | 4/5/2019 2:11:31 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Steve Hill - seam on common vent on north west corner needs sealed - electrical contractor needs to pull a permit
|
MEC18-05250
| Final | 4/5/2019 | 4/5/2019 | 4/5/2019 1:52:34 PM | P | FAIL |
|
|
Lock box code for entry is 1108. Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - need air balance report/ duct blast report/ and stamped man J onsite for final
|
MEC19-01383
| Final | 4/5/2019 | 4/5/2019 | 4/5/2019 1:28:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek - furnace ac coil co ok
|
MEC19-00533
| Final | 4/3/2019 | 4/5/2019 | 4/5/2019 11:49:27 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart - water heater flue and gas line need finished - duct blast document at furnace says system failed -line set UV protection - system needs air balanced and document onsite
|
MEC19-01371
| Final | 4/4/2019 | 4/5/2019 | 4/5/2019 11:38:10 AM | A | PASS |
|
|
Please call Tyrel on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - final ok
|
MEC19-01258
| Rough-in | 4/4/2019 | 4/5/2019 | 4/5/2019 11:37:55 AM | A | PASS |
|
|
Re-inspection of the RI. Phone #: ###-#### Inspection requested via web by Frank Marturello - R/I ok
|
MEC19-01286
| Final | 3/29/2019 | 4/5/2019 | 4/5/2019 10:49:05 AM | A | PASS |
|
|
call home owner before coming Phone #: ###-#### Inspection requested via web by Kim Lithander - A/C coil co ok
|
MEC18-05532
| Rough-in | 4/4/2019 | 4/5/2019 | 4/5/2019 10:32:37 AM | A | PART |
|
|
PRE-ROCK, PARTIAL Phone #: ###-#### Inspection requested via web by Oleg Chervak - east side duct seal ok - east side only R/I ok
|
MEC19-00648
| Final | 4/4/2019 | 4/5/2019 | 4/5/2019 9:58:47 AM | A | PASS |
|
|
Please give us a call when you are on your way so we can notify customer. This is apt number #202. Thank you! Phone #: ###-#### Inspection requested via web by Dan McFate - furnace only co ok
|
MEC19-01279
| Pressure Test | 4/4/2019 | 4/5/2019 | 4/5/2019 9:24:54 AM | A | PASS |
|
|
Flue pressure test and cover - call mike Phone #: ###-#### Inspection requested via web by Brandon Sorensen - 5lb flue pressure test ok
|
MEC19-00162
| Rough-in | 4/4/2019 | 4/5/2019 | 4/5/2019 8:48:36 AM | A | PASS |
|
|
Restrooms 114 and 116 proof for cover and roof top unit 5 // Steve Phone #: ###-#### - R/I on cooridor units 5 and 7 branch runs into classrooms duct seal ok and ok to cover with insulation - restrooms 114 and 116 ok for cover
|
MEC17-05830
| Mec-Aging Inspection | 4/5/2019 | 4/5/2019 | 4/5/2019 8:31:37 AM | | DONE |
|
|
Called Capital City and talked with Max about their mechanical aging permit. Schedule inspection with homeowner if work is done. Permit will expire in 180 days if not active
|
MEC18-03552
| Mec-Aging Inspection | 4/5/2019 | 4/5/2019 | 4/5/2019 8:25:38 AM | | DONE |
|
|
Called Perfect Air and talked with Josh abou their mechanical aging permit. Schedule inspection with homeowner if work is finished. Permit will expire in 180 days if not active
|